Long-time pick-up adjustment type Ir (thermal protection)
|
Réglable 9 positions
|
[Ir] long-time protection pick-up adjustment range
|
160...400 A
|
Long-time protection delay adjustment type tr
|
Réglable
|
[tr] long-time protection delay adjustment range
|
15…400 s à 1,5 x Ir
0,35…11 s à 7,2 x Ir
0,5…16 s à 6 x Ir
|
Mémoire thermique
|
20 minutes avant et après le déclenchement
|
Short-time protection pick-up adjustment type Isd
|
Réglable 9 positions
|
[Isd] Short-time protection pick-up adjustment range
|
1,5...10 x Ir
|
Short-time protection delay adjustment type tsd
|
Réglable
|
[tsd] Short-time protection delay adjustment range
|
0…0,4 s I²t=off
0,1…0,4 s I²t=on
|
Instantaneous protection pick-up adjustment type Ii
|
Réglable
|
[Ii] instantaneous protection pick-up adjustment range
|
1,5...12 x In
|
Protection fuite à la terre
|
Sans
|
Neutral protection settings
|
0,5 x Ir (3t + N/2)
1 x Ir (4t)
1,6 x Ir (3t + OSN)
Aucune protection (3t)
|
Sélectivité logique ZSI
|
Avec
|
Signalisation locale
|
Prêt à fonctionner: DEL clignotante (vert)
Surcharge: DEL 105 % Ir (RED)
Surcharge: DEL 90 % Ir (orange)
|
Type d'afficheur
|
Afficheur LCD
|
Type de mesure
|
Compteur d'énergie
|
Communication des données
|
Valeurs instantanées et de demande
Indicateurs de maintenance
Maximètres/minimètres
Mesure de l'énergie
Demande de courant et puissance
Paramètres de protection et d'alarme
Historiques temps mboutissage et tableaux des événements
Qualité d'alimentation
|
Enregistrement de données
|
Indicateurs de maintenance
|