Long-time pick-up adjustment type Ir (thermal protection)
|
9 mogelijke instellingen
|
[Ir] long-time protection pick-up adjustment range
|
160...400 A
|
Long-time protection delay adjustment type tr
|
Aanpasbaar
|
[tr] long-time protection delay adjustment range
|
15…400 s bij 1.5 x Ir
0,35…11 s bij 7.2 x Ir
0,5…16 s bij 6 x Ir
|
Thermisch geheugen
|
20 minuten voor en na uitschakeling
|
Short-time protection pick-up adjustment type Isd
|
Aanpasbaar
|
[Isd] Short-time protection pick-up adjustment range
|
1.5...10 x Ir
|
Short-time protection delay adjustment type tsd
|
Aanpasbaar
|
[tsd] Short-time protection delay adjustment range
|
0…0,4 s I²t=off
0,1…0,4 s I²t=on
|
Instantaneous protection pick-up adjustment type Ii
|
Aanpasbaar
|
[Ii] instantaneous protection pick-up adjustment range
|
1.5...11 x In Compact NSX630
1.5...12 x In Compact NSX400
|
Ground-fault protection pick-up adjustment type Ig
|
Aanpasbaar
|
[Ig] ground-fault protection pick-up adjustment range
|
0.4...1 x In voor In = 40 A
0.2...1 x In voor In>40A
Ig inschakelen aan/uit
|
Ground-fault protection time delay adjustment type tg
|
Aanpasbaar
|
[tg] ground-fault protection time delay adjustment range
|
0…0,4 s I²t=off
0,1…0,4 s I²t=on
|
Differentieelfunctie
|
Zonder
|
Zone selectieve vergrendelings-ZSI
|
Met
|
Lokale signalering
|
Voor klaar voor bedrijf: knipperende LED (groene)
Voor overbelasting: led 105% Ir (rood)
Voor overbelasting: Led 90% lr (oranje)
|
Displaytype
|
Lcd-display
|
Type meting
|
Ampèremeter
|
Communicatie van data
|
Stroomkwaliteit
Energiemeting
Verbruiksstroom en vermogen
Historiek- en gebeurtenissentabel met tijdstempel
Beveiligings- en alarminstellingen
Maximeters/minimeters
Onderhoudsindicators
Onmiddellijke waarden en waarden op aanvraag
|
Elektrische gegevensregistratie
|
Onderhoudsindicators
|