Long-time pick-up adjustment type Ir (thermal protection)
|
Justerbar 9 indstillinger
|
[Ir] long-time protection pick-up adjustment range
|
"63...160 A"
|
Long-time protection delay adjustment type tr
|
Justerbar
|
[tr] long-time protection delay adjustment range
|
15…400 sekund ved 1.5 x Ir
0,35…11 sekund ved 7.2 x Ir
0,5…16 sekund ved 6 x Ir
|
Termisk hukommelse
|
20 minutter før og efter udløsning
|
Short-time protection pick-up adjustment type Isd
|
Justerbar 9 indstillinger
|
[Isd] Short-time protection pick-up adjustment range
|
1.5...10 x Ir
|
Short-time protection delay adjustment type tsd
|
Justerbar
|
[tsd] Short-time protection delay adjustment range
|
0…0,4 sekund "I²t=off"
0,1…0,4 sekund "I²t=on"
|
Instantaneous protection pick-up adjustment type Ii
|
Justerbar
|
[Ii] instantaneous protection pick-up adjustment range
|
1.5...15 x In
|
Fejlstrømsbeskyttelse
|
Uden
|
Zone selective låsing ZSI
|
Med
|
Lokal indikering
|
For klar til betjening: flashing LED (grøn)
For overbelastning: LED 105 % Ir (rød)
For overbelastning: LED 90 % Ir (orange)
|
Skærmtype
|
LCD skærm
|
Måletype
|
Energimåler
|
Datakommunikation
|
Energi metering
Beskyttelse og alarm indstillinger
Tids-stemplet historie og hændelsetabeller
Øjeblikkelig og demand values
Vedligeholdelse indikatorer
Demand strøm og strøm
Strøm kvalitet
Maximeters/minimeters
|
Opsamling af eelektriské data
|
Serviceindikator
|