Long-time pick-up adjustment type Ir (thermal protection)
|
Justerbar 9 indstillinger
|
[Ir] long-time protection pick-up adjustment range
|
"63...160 A"
|
Long-time protection delay adjustment type tr
|
Justerbar
|
[tr] long-time protection delay adjustment range
|
15…400 sekund ved 1.5 x Ir
0,35…11 sekund ved 7.2 x Ir
0,5…16 sekund ved 6 x Ir
|
Neutral protection settings
|
0.5 x Ir (3d + N/2)
1 x Ir ("4d")
1.6 x Ir (3D + OSN)
Ingen beskyttelse ("3d")
|
Termisk hukommelse
|
20 minutter før og efter udløsning
|
Short-time protection pick-up adjustment type Isd
|
Justerbar
|
[Isd] Short-time protection pick-up adjustment range
|
1.5...10 x Ir
|
Short-time protection delay adjustment type tsd
|
Justerbar
|
[tsd] Short-time protection delay adjustment range
|
0…0,4 sekund "I²t=off"
0,1…0,4 sekund "I²t=on"
|
Instantaneous protection pick-up adjustment type Ii
|
Justerbar
|
[Ii] instantaneous protection pick-up adjustment range
|
1.5...15 x In
|
Fejlstrømsbeskyttelse
|
Integreret
|
Følsomhedsklasse
|
Klasse A
|
Earth-leakage protection sensitity adjustment type IΔn
|
Justerbar
|
[IΔn] earth-leakage protection sensitivity adjustment range
|
0,03 A
0,1 A
0,3 A
0,5 A
1 A
3 A
5 A
|
Earth-leakage protection specific mode
|
OFF using the IΔn rotary switch
|
Earth-leakage protection time delay adjustement type Δt
|
Justerbar
|
[Δt] Earth-leakage protection time delay adjustment range
|
0 milisekund
60 milisekund
150 milisekund
500 milisekund
1 sekund
|
Zone selective låsing ZSI
|
Uden
|
Lokal indikering
|
For klar til betjening: flashing LED (grøn)
For overbelastning: LED 105 % Ir (rød)
For overbelastning: LED 90 % Ir (orange)
|
Skærmtype
|
LCD skærm
|
Måletype
|
Energimåler
|
Datakommunikation
|
Maximeters/minimeters
Strøm kvalitet
Earth leakage current
Beskyttelse og alarm indstillinger
Øjeblikkelig og demand values
Energi metering
Tids-stemplet historie og hændelsetabeller
Demand strøm og strøm
Test reports
Vedligeholdelse indikatorer
|