Long-time pick-up adjustment type Ir (thermal protection)
|
Justerbar
|
[Ir] long-time protection pick-up adjustment range
|
"250...630 A"
|
Long-time protection delay adjustment type tr
|
Justerbar
|
[tr] long-time protection delay adjustment range
|
15…400 sekund ved 1.5 x Ir
0,35…11 sekund ved 7.2 x Ir
0,5…16 sekund ved 6 x Ir
|
Neutral protection settings
|
0.5 x Ir (3d + N/2)
1 x Ir ("4d")
1.6 x Ir (3D + OSN)
Ingen beskyttelse ("3d")
|
Termisk hukommelse
|
20 minutter før og efter udløsning
|
Short-time protection pick-up adjustment type Isd
|
Justerbar
|
[Isd] Short-time protection pick-up adjustment range
|
1.5...10 x Ir
|
Short-time protection delay adjustment type tsd
|
Justerbar
|
[tsd] Short-time protection delay adjustment range
|
0…0,4 sekund "I²t=off"
0,1…0,4 sekund "I²t=on"
|
Instantaneous protection pick-up adjustment type Ii
|
Justerbar
|
[Ii] instantaneous protection pick-up adjustment range
|
1.5...11 x In
|
Ground-fault protection pick-up adjustment type Ig
|
Justerbar
|
[Ig] ground-fault protection pick-up adjustment range
|
0.4...1 x In til "In = 40 A"
0.2...1 x In til "In > 40 A"
Ig enable on/off
|
Ground-fault protection time delay adjustment type tg
|
Justerbar
|
[tg] ground-fault protection time delay adjustment range
|
0…0,4 sekund "I²t=off"
0,1…0,4 sekund "I²t=on"
|
Fejlstrømsbeskyttelse
|
Uden
|
Zone selective låsing ZSI
|
Med
|
Lokal indikering
|
For klar til betjening: flashing LED (grøn)
For overbelastning: LED 105 % Ir (rød)
For overbelastning: LED 90 % Ir (orange)
|
Skærmtype
|
LCD skærm
|
Måletype
|
Energimåler
|
Datakommunikation
|
Energi metering
Beskyttelse og alarm indstillinger
Tids-stemplet historie og hændelsetabeller
Øjeblikkelig og demand values
Vedligeholdelse indikatorer
Demand strøm og strøm
Strøm kvalitet
Maximeters/minimeters
|
Opsamling af eelektriské data
|
Serviceindikator
|