Long-time pick-up adjustment type Ir (thermal protection)
|
Justerbar 9 innstillinger
|
[Ir] long-time protection pick-up adjustment range
|
18...40 A
|
Long-time protection delay adjustment type tr
|
Justerbar
|
[tr] long-time protection delay adjustment range
|
15…400 s på 1.5 x Ir
0,35…11 s på 7.2 x Ir
0,5…16 s på 6 x Ir
|
Termisk minne
|
20 min før og etter utkobling
|
Short-time protection pick-up adjustment type Isd
|
Justerbar 9 innstillinger
|
[Isd] Short-time protection pick-up adjustment range
|
1.5...10 x Ir
|
Short-time protection delay adjustment type tsd
|
Justerbar
|
[tsd] Short-time protection delay adjustment range
|
0…0,4 s I²t=off
0,1…0,4 s I²t=on
|
Instantaneous protection pick-up adjustment type Ii
|
Justerbar
|
[Ii] instantaneous protection pick-up adjustment range
|
1.5...12 x In Compact NSX250
1.5...15 x In Compact NSX100
1.5...15 x In Compact NSX160
|
Ground-fault protection pick-up adjustment type Ig
|
Justrbar
|
[Ig] ground-fault protection pick-up adjustment range
|
0.4...1 x In for In = 40 A
0.2...1 x In for In > 40 A
Ig enable on/off
|
Ground-fault protection time delay adjustment type tg
|
Justrbar
|
[tg] ground-fault protection time delay adjustment range
|
0…0,4 s I²t=off
0,1…0,4 s I²t=on
|
Jordfeilbeskyttelse
|
Uten
|
Neutral protection settings
|
0.5 x Ir ( 3t + N/2)
1 x Ir ( 4t)
1.6 x Ir ( 3t + OSN)
Uten vern ( 3t)
|
Zone selektiv forrigling (logisk selektivitet) ZSI
|
Med
|
Lokal varsling
|
Klar til drift: flashing LED ( grønn)
Overbelastning: LED 105 % Ir ( rød)
Overbelastning: LED 90 % Ir ( oransje)
|
Skjermtype
|
LCD display
|
Type måling
|
Energimåler
|
Datakommunikasjon
|
Energimåling
Gjennomsnitts strøm og effekt
Tidsstemplet historikk og hendelsestabeller
Vern og alarm innstillinger
Vedlikeholdsindikatorer
Nettkvalitet
Momentan og gjennomsnitts verdier
Maks/minimeter
|
Lagring av elektriske data
|
Vedlikeholdsindikatorer
|