Long-time pick-up adjustment type Ir (thermal protection)
|
Réglable 9 positions
|
[Ir] long-time protection pick-up adjustment range
|
100...250 A
|
Long-time protection delay adjustment type tr
|
Réglable
|
[tr] long-time protection delay adjustment range
|
15…400 s à 1,5 x Ir
0,35…11 s à 7,2 x Ir
0,5…16 s à 6 x Ir
|
Mémoire thermique
|
20 minutes avant et après le déclenchement
|
Short-time protection pick-up adjustment type Isd
|
Réglable
|
[Isd] Short-time protection pick-up adjustment range
|
1,5...10 x Ir
|
Short-time protection delay adjustment type tsd
|
Réglable
|
[tsd] Short-time protection delay adjustment range
|
0…0,4 s
|
Instantaneous protection pick-up adjustment type Ii
|
Réglable
|
[Ii] instantaneous protection pick-up adjustment range
|
3000 A
|
Protection différentielle
|
Intégrée
|
Classe de protection différentielle
|
Classe A
|
Earth-leakage protection sensitity adjustment type IΔn
|
Réglable
|
[IΔn] earth-leakage protection sensitivity adjustment range
|
500 mA
5 A
1 A
100 mA
3 A
30 mA
300 mA
|
Earth-leakage protection specific mode
|
Off utilisation de l'interrupteur rotatif IΔn
|
Earth-leakage protection time delay adjustement type Δt
|
Réglable
|
[Δt] Earth-leakage protection time delay adjustment range
|
500 ms
150 ms
0 ms
60 ms
1 s
|
Neutral protection settings
|
0,5 x Ir (3t + N/2)
1 x Ir (4t)
1,6 x Ir (3t + OSN)
Aucune protection (3t)
|
Zone de verrouillage sélectif logique ZSI
|
Sans
|
Signalisation locale
|
Pourprêt à fonctionner DEL clignotante (vert)
Poursurcharge DEL 105 % Ir (rouge)
Poursurcharge DEL 90 % Ir (orange)
|
Type d'afficheur
|
Afficheur LCD
|
Type de mesure
|
Compteur d'énergie
|
Communication des données
|
Maximètres/minimètres
Rapport de test
Demande de courant et puissance
Paramètres de protection et d'alarme
Valeurs instantanées et de demande
Historiques temps emboutissage et tableaux des événements
Mesure de l'énergie
Indicateurs de maintenance
Conduit de fuite à la terre
Qualité d'alimentation
|