Long-time pick-up adjustment type Ir (thermal protection)
|
Regolabile, 9 valori
|
[Ir] long-time protection pick-up adjustment range
|
"250...570 A"
|
Long-time protection delay adjustment type tr
|
Fissa
|
[tr] long-time protection delay adjustment range
|
11 s a 7,2 x Ir
16 s a 6 x Ir
400 s a 1,5 x Ir
|
Memoria termica
|
20 minuti prima e dopo lo scatto
|
Short-time protection pick-up adjustment type Isd
|
Regolabile
|
[Isd] Short-time protection pick-up adjustment range
|
1.5...10 x Ir
|
Short-time protection delay adjustment type tsd
|
Fissa
|
[tsd] Short-time protection delay adjustment range
|
0,02 s
|
Instantaneous protection pick-up adjustment type Ii
|
Fissa
|
[Ii] instantaneous protection pick-up adjustment range
|
6900 A
|
Protezione differenziale
|
Integrato
|
Tipo di protezione differenziale
|
Classe A
|
Earth-leakage protection sensitity adjustment type IΔn
|
Regolabile
|
[IΔn] earth-leakage protection sensitivity adjustment range
|
10 A
300 mA
5 A
1 A
3 A
500 mA
|
Earth-leakage protection specific mode
|
OFF using the IΔn rotary switch
|
Earth-leakage protection time delay adjustement type Δt
|
Regolabile
|
[Δt] Earth-leakage protection time delay adjustment range
|
60 ms
0 ms
150 ms
500 ms
1 s
|
Selettività logica ZSI
|
Senza
|
Segnalazione locale
|
LED lampeggiante (verde)pronto al funzionamento:
LED 105% Ir (rosso)Sovraccarico:
LED 90% Ir (arancione)Sovraccarico:
Indicatore colore (giallo)corrente residua:
|