Type of operating handle
|
Direct right side
|
Mounting support
|
Plate
|
[Ui] rated insulation voltage
|
750 V AC 50/60 Hz
|
[Uimp] rated impulse withstand voltage
|
8 kV
|
Rated operational power in W
|
132 kW at 400 V
160 kW at 500 V
220 kW at 690 V
|
Breaking capacity
|
23 W
|
Making capacity
|
2500 A at 400 V AC-23B
|
Breaking capacity
|
2000 A at 400 V (AC-23B)
|
Short-circuit withstand
|
32.5 kA
|
Mechanical durability
|
10000 cycles
|
Electrical durability
|
1000 cycles AC-23A
1000 cycles AC-23B
200 cycles DC-23A
200 cycles DC-23B
|
Connections - terminals
|
Power circuit: bars
Power circuit: lugs-ring terminals95…240 mm² flexible
|
[Icm] rated short-circuit making capacity
|
100 kA at 400 V with protection by gG fuses
|
Tightening torque
|
Power circuit: 25 N.m - on bars
Power circuit: 25 N.m - on lugs-ring terminals
|