[Ue] rated operational voltage
|
240 V AC 50/60 Hz
415 V AC 50/60 Hz
440 V AC 50/60 Hz
|
Magnetic tripping limit
|
8.5 x In +/- 20 % AC
|
[Ics] rated service breaking capacity
|
4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC
7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC
15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC
4.5 kA 75 % conforming to GB 14048.2 - 440 V AC
7.5 kA 75 % conforming to GB 14048.2 - 415 V AC
15 kA 75 % conforming to GB 14048.2 - 240 V AC
|
[Ui] rated insulation voltage
|
500 V AC conforming to EN/IEC 60947-2
|
[Uimp] rated impulse withstand voltage
|
6 kV conforming to EN/IEC 60947-2
|
Suitability for isolation
|
Yes conforming to EN/IEC 60947-2
|
Contact position indicator
|
Yes
|
Control type
|
Toggle
|
Local signalling
|
ON/OFF indication
|
Mounting mode
|
Clip-on
|
Mounting support
|
DIN rail
|
9 mm pitches
|
8
|
Height
|
81 mm
|
Width
|
72 mm
|
Depth
|
72 mm
|
Colour
|
Grey
|
Mechanical durability
|
20000 cycles
|
Electrical durability
|
10000 cycles
|
Provision for padlocking
|
Padlockable
|
Connections - terminals
|
Tunnel type terminal (top or bottom)1…25 mm² (AWG 18...AWG 8) - rigid
Tunnel type terminal (top or bottom)1…16 mm² (AWG 18...AWG 8) - flexible with ferrule
Tunnel type terminal (top or bottom)1…16 mm² (AWG 18...AWG 8) - flexible
|
Wire stripping length
|
14 mm for top or bottom connection
|
Tightening torque
|
2.5 N.m top or bottom
|
Earth-leakage protection
|
Without
|