Network frequency
|
50/60 Hz
|
Control type
|
Push-button
|
Mounting mode
|
Fixed
|
[In] rated current
|
4000 A at 40 °C
|
[Ui] rated insulation voltage
|
1000 V AC 50/60 Hz conforming to IEC 60947-2
|
[Uimp] rated impulse withstand voltage
|
12 kV conforming to IEC 60947-2
|
[Icm] rated short-circuit making capacity
|
143 kA 525 V AC at 50/60 Hz
143 kA 690 V AC at 50/60 Hz
|
[Ue] rated operational voltage
|
690 V AC 50/60 Hz conforming to IEC 60947-2
|
Circuit breaker CT rating
|
4000 A
|
Breaking capacity
|
65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
|
[Ics] rated service breaking capacity
|
65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
|
Protection type
|
Without protection
|
Mechanical durability
|
10000 cycles without maintenance conforming to IEC 60947-2
20000 cycles with maintenance conforming to IEC 60947-2
|
Electrical durability
|
AC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
|
Connection pitch
|
150 mm
|
[Icw] rated short-time withstand current
|
65 kA 1 s conforming to IEC 60947-2
65 kA 3 s conforming to IEC 60947-2
|
Maximum breaking time
|
25 ms
|
Maximum closing response time
|
70 ms
|
Height
|
352 mm
|
Width
|
422 mm
|
Depth
|
297 mm
|