Long-time pick-up adjustment type Ir (thermal protection)
|
9 nastavitev
|
[Ir] long-time protection pick-up adjustment range
|
63 do 160 A
|
Long-time protection delay adjustment type tr
|
Pritrjen
|
[tr] long-time protection delay adjustment range
|
11 s pri7,2 x Ir
16 s pri6 x Ir
400 s pri1,5 x Ir
|
Toplotni spomin
|
20 minut pred in po izklopu
|
Short-time protection pick-up adjustment type Isd
|
9 nastavitev
|
[Isd] Short-time protection pick-up adjustment range
|
1,5 do 10 x Ir
|
Short-time protection delay adjustment type tsd
|
Pritrjen
|
Instantaneous protection pick-up adjustment type Ii
|
Pritrjen
|
[Ii] instantaneous protection pick-up adjustment range
|
2400 A
|
Zemljostična zaščita
|
Brez
|
Območje selektivne blokade ZSI
|
Brez
|
Lokalno signaliziranje
|
ZaPripravljen za obratovanje Utripajo?a LED ( Zelena)
ZaPreobremenitev LED 105 % Ir ( Rde?a)
ZaPreobremenitev LED 90 % Ir ( Oran?na)
|