Long-time pick-up adjustment type Ir (thermal protection)
|
9 nastavitev
|
[Ir] long-time protection pick-up adjustment range
|
63 do 160 A
|
Long-time protection delay adjustment type tr
|
Nastavljiv
|
[tr] long-time protection delay adjustment range
|
15…400 s pri1,5 x Ir
0,35…11 s pri7,2 x Ir
0,5…16 s pri6 x Ir
|
Toplotni spomin
|
20 minut pred in po izklopu
|
Short-time protection pick-up adjustment type Isd
|
9 nastavitev
|
[Isd] Short-time protection pick-up adjustment range
|
1,5 do 10 x Ir
|
Short-time protection delay adjustment type tsd
|
Nastavljiv
|
[tsd] Short-time protection delay adjustment range
|
0…0,4 s I²t=off
0,1…0,4 s I²t=on
|
Instantaneous protection pick-up adjustment type Ii
|
Nastavljiv
|
[Ii] instantaneous protection pick-up adjustment range
|
1,5 do 15 x In
|
Ground-fault protection pick-up adjustment type Ig
|
Nastavljiv
|
[Ig] ground-fault protection pick-up adjustment range
|
0,4 do 1 x In zaIn = 40 A
0,2 do 1 x In zaIn > 40 A
Ig omogočeno ON/OFF
|
Ground-fault protection time delay adjustment type tg
|
Nastavljiv
|
[tg] ground-fault protection time delay adjustment range
|
0…0,4 s I²t=off
0,1…0,4 s I²t=on
|
Zemljostična zaščita
|
Brez
|
Območje selektivne blokade ZSI
|
Z
|
Lokalno signaliziranje
|
ZaPripravljen za obratovanje Utripajoča LED ( Zelena)
ZaPreobremenitev LED 105 % Ir ( Rdeča)
ZaPreobremenitev LED 90 % Ir ( Oranžna)
|
Tip zaslona
|
LCD zaslon
|
Tip meritev
|
Merilnik energije
|
Sporočanje podatkov
|
Merjenje energije
Nastavitve zaščite in alarma
Časovno ožigosana zgodovina in tabele dogodkov
Trenutne in skupne vrednosti
Kazalniki vzdrževanja
Poraba moči in toka
Kvaliteta energije
Maksimetri/minimetri
|
Beleženje električnih podatkov
|
Kazalniki vzdrževanja
|