Long-time pick-up adjustment type Ir (thermal protection)
|
9 nastavitev
|
[Ir] long-time protection pick-up adjustment range
|
160 do 400 A
|
Long-time protection delay adjustment type tr
|
Nastavljiv
|
[tr] long-time protection delay adjustment range
|
15…400 s pri1,5 x Ir
0,35…11 s pri7,2 x Ir
0,5…16 s pri6 x Ir
|
Toplotni spomin
|
20 minut pred in po izklopu
|
Short-time protection pick-up adjustment type Isd
|
Nastavljiv
|
[Isd] Short-time protection pick-up adjustment range
|
1,5 do 10 x Ir
|
Short-time protection delay adjustment type tsd
|
Nastavljiv
|
[tsd] Short-time protection delay adjustment range
|
0…0,4 s I²t=off
0,1…0,4 s I²t=on
|
Instantaneous protection pick-up adjustment type Ii
|
Nastavljiv
|
[Ii] instantaneous protection pick-up adjustment range
|
1,5 do 12 x In
|
Zemljostična zaščita
|
Integriran
|
Razred zemljostične zaščite
|
Razred A
|
Earth-leakage protection sensitity adjustment type IΔn
|
Nastavljiv
|
[IΔn] earth-leakage protection sensitivity adjustment range
|
0,3 A
0,5 A
1 A
3 A
5 A
10 A
|
Earth-leakage protection specific mode
|
Off using the IΔn rotary switch
|
Earth-leakage protection time delay adjustement type Δt
|
Nastavljiv
|
[Δt] Earth-leakage protection time delay adjustment range
|
0 ms
60 ms
150 ms
500 ms
1 s
|
Območje selektivne blokade ZSI
|
Brez
|
Lokalno signaliziranje
|
ZaPripravljen za obratovanje Utripajoča LED ( Zelena)
ZaPreobremenitev LED 105 % Ir ( Rdeča)
ZaPreobremenitev LED 90 % Ir ( Oranžna)
|
Tip zaslona
|
LCD zaslon
|
Tip meritev
|
Merilnik energije
|
Sporočanje podatkov
|
Kazalniki vzdrževanja
Trenutne in skupne vrednosti
Časovno ožigosana zgodovina in tabele dogodkov
Kvaliteta energije
Merjenje energije
Test reports
Maksimetri/minimetri
Poraba moči in toka
Earth leakage current