Schneider-Electric Riverbank Electrical Wholesalers Ltd
 
ABL8RPS24050 picture- Schneider-electric
ABL8RPS24050
regulated SMPS - 1 or 2-phase - 100..500 V - 24 V - 5 A
Schneider Electric
Characteristics
Main
Range of product Phaseo
Product or component type Power supply
Power supply type Regulated switch mode
Input voltage 100...120 V AC single phase, terminal(s): N-L1
200...500 V AC phase to phase, terminal(s): L1-L2
Output voltage 24 V DC
Rated power in W 120 W
Provided equipment Power factor correction filter conforming to IEC 61000-3-2
Power supply output current 5 A
Output protection type Against overload, protection technology: manual or automatic reset
Against overvoltage, protection technology: 30...32 V, manual reset
Against short-circuits, protection technology: manual or automatic reset
Against undervoltage, protection technology: tripping if U < 21.6 V
Thermal, protection technology: automatic reset
Ambient air temperature for operation 50…60 °C (with derating factor)
-25…50 °C (without)
Complementary
Input voltage limits 85...132 V
170...550 V
Network frequency 47...63 Hz
Inrush current 30 A 2 ms
Cos phi 0.51 at 240 V
0.59 at 120 V
Efficiency 87 %
Output voltage limits 24...28.8 V adjustable
Power dissipation in W 15.5 W
Line and load regulation 1...3 %
Holding time >= 120 ms at 400 V
>= 20 ms at 100 V
>= 40 ms at 240 V
Permissible temporary current boost 1.5 x In (for 4 s)
Connections - terminals For diagnostic relay: removable screw terminal block, connection capacity: 2 x 2.5 mm²
For input connection: screw type terminals, connection capacity: 3 x 0.5...3 x 4 mm² AWG 22...AWG 12
For input ground connection: screw type terminals, connection capacity: 1 x 0.5...1 x 4 mm² AWG 22...AWG 12
For output connection: screw type terminals, connection capacity: 4 x 0.5...4 x 4 mm² AWG 22...AWG 12
For output ground connection: screw type terminals, connection capacity: 1 x 0.5...1 x 4 mm² AWG 22...AWG 12
Marking CE
Mounting support 35 x 15 mm symmetrical DIN rail
35 x 7.5 mm symmetrical DIN rail
Operating position Vertical
Operating altitude 2000 m
Output coupling Parallel
Series
Name of test Electrostatic discharges conforming to EN/IEC 61000-4-2
Induced electromagnetic field conforming to EN/IEC 61000-4-6
Magnetic field conforming to EN 61000-4-8
Primary outage conforming to IEC 61000-4-11
Radiated electromagnetic field conforming to EN/IEC 61000-4-3
Rapid transient conforming to IEC 61000-4-4
Surge conforming to EN/IEC 61000-4-5
Conducted emissions on the power line conforming to EN 55022 class B
Radiated emissions conforming to EN 55022 class B
Harmonic current emission conforming to EN/IEC 61000-3-2
Status LED 1 LED (green and red)output voltage:
1 LED (green, red and orange)output current:
Depth 125 mm
Height 143 mm
Width 56 mm
Net weight 0.7 kg
Environment
MTBF reliability 915000 H at 100 V AC with UTE C80-810 calculation method
950000 H at 200...500 V AC with UTE C80-810 calculation method
Product certifications CCSAus
EAC
KC
RCM
UL
Standards CSA C22.2 No 60950-1
UL 508
Environmental characteristic EMC conforming to EN 61000-6-1
EMC conforming to EN 61000-6-3
EMC conforming to EN 55024
EMC conforming to EN/IEC 61000-6-4
EMC conforming to EN/IEC 61204-3
Safety conforming to EN/IEC 60950-1
Safety conforming to EN/IEC 61204-3
Safety conforming to SELV
IP degree of protection IP20 conforming to EN/IEC 60529
Ambient air temperature for storage -40…70 °C
Relative humidity 0…90 % during operation
0…95 % in storage
Overvoltage category Class I conforming to VDE 0106-1
Dielectric strength 3500 V between input and ground
4000 V between input and output
500 V between output and ground
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation
print REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
print EU RoHS Declaration
Mercury free Yes
RoHS exemption information
print Yes
China RoHS Regulation
print China RoHS declaration
Environmental Disclosure
print Product Environmental Profile
Circularity Profile
print End of Life Information
Contractual warranty
Warranty 18 months