Network Frequency
|
50 Hz
|
[Ue] rated operational voltage
|
400 V AC 50 Hz
|
Maximum power
|
2.1 W 400 V AC
|
[Ui] rated insulation voltage
|
500 V AC 50/60 Hz
|
[Uimp] rated impulse withstand voltage
|
4 kV
|
Control signal type
|
Maintained
|
Switching frequency
|
100 switching operations/day
|
Local signalling
|
Action indicator
|
Hold-in power consumption in VA
|
6.5 VA
|
Inrush power in VA
|
53 VA
|
Mounting Mode
|
Clip-on
|
Mounting Support
|
35 mm symmetrical DIN rail
|
9 mm pitches
|
6
|
Height
|
3.3 in (85 mm)
|
Width
|
2.1 in (54 mm)
|
Depth
|
2.4 in (60 mm)
|
Color
|
White
|
Mechanical durability
|
1000000 cycles
|
Electrical durability
|
100000 cycles IEC/EN 61095 63 A 50 Hz AC-7A
30000 cycles IEC/EN 61095 20 A 50 Hz AC-7B
30000 cycles IEC/EN 61095 50 Hz AC-7C
100000 cycles EN/IEC 60947-4-1 50 Hz AC-1
30000 cycles EN/IEC 60947-4-1 50 Hz AC-3
30000 cycles EN/IEC 60947-4-1 50 Hz AC-5a
30000 cycles EN/IEC 60947-4-1 50 Hz AC-5b
|
Connections - terminals
|
Control circuit tunnel type terminals 2 0.002 in² (1.5 mm²) rigid
Control circuit tunnel type terminals 1 0.002…0.004 in² (1.5…2.5 mm²) rigid
Power circuit tunnel type terminals 1 0.009…0.02 in² (6…16 mm²) flexible
Power circuit tunnel type terminals 1 0.009…0.04 in² (6…25 mm²) rigid
Control circuit tunnel type terminals 2 0.002…0.004 in² (1.5…2.5 mm²) flexible
|
Tightening torque
|
Control circuit: 7.08 lbf.in (0.8 N.m)
Power circuit: 31.0 lbf.in (3.5 N.m)
|
Product Compatibility
|
IACTc
IATEt
IACTs
IACTp
|
Compatibility code
|
ICT
|
Market Segment
|
Residential
Small commercial
|