Device Application
|
Distribution
|
Range
|
Acti9
|
Product name
|
Acti9 iC60
|
Product or Component Type
|
Miniature circuit-breaker
|
Device short name
|
IC60N
|
Poles description
|
3P
|
Number of protected poles
|
3
|
Line Rated Current
|
25 A
|
Network type
|
AC
DC
|
Trip unit technology
|
Thermal-magnetic
|
Curve code
|
C
|
Breaking capacity
|
6000 A Icn 400 V AC 50/60 Hz EN/IEC 60898-1
36 kA Icu 12...133 V AC 50/60 Hz EN/IEC 60947-2
10 kA Icu <= 180 V DC EN/IEC 60947-2
10 kA Icu 380...415 V AC 50/60 Hz EN/IEC 60947-2
20 kA Icu 220...240 V AC 50/60 Hz EN/IEC 60947-2
6 kA Icu 440 V AC 50/60 Hz EN/IEC 60947-2
|
Utilisation category
|
Category A EN 60898-1
Category A IEC 60898-1
|
Suitability for isolation
|
Yes EN 60898-1
Yes EN 60947-2
Yes IEC 60898-1
Yes IEC 60947-2
|
Standards
|
EN 60898-1
IEC 60947-2
IEC 60898-1
EN 60947-2
|
Network Frequency
|
50/60 Hz
|
Magnetic tripping limit
|
8 x In +/- 20 %
|
[Ics] rated service breaking capacity
|
15 kA 75 % EN 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 75 % EN 60947-2 - 380...415 V AC 50/60 Hz
4.5 kA 75 % EN 60947-2 - 440 V AC 50/60 Hz
15 kA 75 % IEC 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 75 % IEC 60947-2 - 380...415 V AC 50/60 Hz
4.5 kA 75 % IEC 60947-2 - 440 V AC 50/60 Hz
27 kA 75 % IEC 60947-2 - 12...133 V AC 50/60 Hz
27 kA 75 % EN 60947-2 - 12...133 V AC 50/60 Hz
6000 A 100 % EN 60898-1 - 400 V AC 50/60 Hz
6000 A 100 % IEC 60898-1 - 400 V AC 50/60 Hz
10 kA 100 % IEC 60947-2 - 125...180 V DC
10 kA 100 % EN 60947-2 - 125...180 V DC
|
Limitation class
|
3 EN 60898-1
3 IEC 60898-1
|
[Ui] rated insulation voltage
|
500 V AC 50/60 Hz EN 60947-2
500 V AC 50/60 Hz IEC 60947-2
|
[Uimp] rated impulse withstand voltage
|
6 kVEN 60947-2
6 kVIEC 60947-2
|
Contact position indicator
|
Yes
|
Control Type
|
Toggle
|
Local signalling
|
Trip indicator
|
Mounting Support
|
DIN rail
|
9 mm pitches
|
6
|
Height
|
3.6 in (91 mm)
|
Width
|
2.1 in (54 mm)
|
Depth
|
3.09 in (78.5 mm)
|
Net Weight
|
0.827 lb(US) (0.375 kg)
|
Color
|
White
|
Mechanical durability
|
20000 cycles
|
Electrical durability
|
10000 cycles
|
Connections - terminals
|
Double terminal top or bottom) 0.002…0.04 in² (1…25 mm²) rigid
Double terminal top or bottom) 0.002…0.02 in² (1…16 mm²) flexible
|
Wire stripping length
|
0.6 in (14 mm) for top or bottom connection
|
Tightening torque
|
17.7 lbf.in (2 N.m) top or bottom
|
Earth-leakage protection
|
Separate block
|