Poles description
|
3P
|
Network type
|
AC
|
Utilisation category
|
Category A IEC 60947-2
AC-3 IEC 60947-4-1
AC-3e IEC 60947-4-1
|
Network frequency
|
50/60 Hz IEC 60947-2
|
Motor power kW
|
1.1 kW 400/415 V AC 50/60 Hz
1.5 kW 400/415 V AC 50/60 Hz
1.5 kW 500 V AC 50/60 Hz
3 kW 690 V AC 50/60 Hz
|
Breaking capacity
|
100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2
100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2
100 kA Icu 440 V AC 50/60 Hz IEC 60947-2
100 kA Icu 500 V AC 50/60 Hz IEC 60947-2
4 kA Icu 690 V AC 50/60 Hz IEC 60947-2
|
[Ics] rated service short-circuit breaking capacity
|
100 % 230/240 V AC 50/60 Hz IEC 60947-2
100 % 400/415 V AC 50/60 Hz IEC 60947-2
100 % 440 V AC 50/60 Hz IEC 60947-2
100 % 500 V AC 50/60 Hz IEC 60947-2
100 % 690 V AC 50/60 Hz IEC 60947-2
|
Control Type
|
Rotary handle
|
Line Rated Current
|
4 A
|
Thermal protection adjustment range
|
2.5…4 A IEC 60947-4-1
|
Magnetic tripping current
|
74 A
|
[Ith] conventional free air thermal current
|
4 A IEC 60947-4-1
|
[Ue] rated operational voltage
|
690 V AC 50/60 Hz IEC 60947-2
|
[Ui] rated insulation voltage
|
690 V AC 50/60 Hz IEC 60947-2
|
[Uimp] rated impulse withstand voltage
|
6 kV IEC 60947-2
|
Suitability for isolation
|
Yes IEC 60947-1
|
Power dissipation per pole
|
1.8 W
|
Mechanical durability
|
100000 cycles
|
Electrical durability
|
100000 cycles AC-3 415 V In
100000 cycles AC-3e 415 V In
|
Rated duty
|
Continuous IEC 60947-4-1
|
Tightening torque
|
15.05 lbf.in (1.7 N.m) screw clamp terminal
|
Fixing mode
|
35 mm symmetrical DIN rail clipped
Panel screwed with 2 x M4 screws)
|
Mounting position
|
Horizontal
Vertical
|
Width
|
1.8 in (45 mm)
|
Height
|
3.5 in (89 mm)
|
Depth
|
3.8 in (97 mm)
|
Net Weight
|
0.73 lb(US) (0.33 kg)
|
Color
|
Dark grey
|