[Ui] rated insulation voltage
|
600 V UL 508
690 V IEC 60947-1
600 V CSA C22.2 No 14
|
[Ue] rated operational voltage
|
48...690 V AC
24...240 V DC
|
[Ith] conventional free air thermal current
|
6 A
|
Mechanical durability
|
100000 cycles
|
Minimum switching current
|
5 mA
|
Minimum switching voltage
|
17 V
|
Protection type
|
GB2CB... circuit breaker
GG fuse 10 A
|
Rated operational power in VA
|
300 VA 48 V AC-15 100000 cycles
414 VA 690 V AC-15 100000 cycles
500 VA 110…127 V AC-15 100000 cycles
500 VA 500 V AC-15 100000 cycles
650 VA 440 V AC-15 100000 cycles
720 VA 230…240 V AC-15 100000 cycles
850 VA 380…415 V AC-15 100000 cycles
|
Rated operational power in W
|
120 W 240 V DC-13 100000 cycles
140 W 110 V DC-13 100000 cycles
140 W 24 V DC-13 100000 cycles
180 W 60 V DC-13 100000 cycles
240 W 48 V DC-13 100000 cycles
|
Tightening torque
|
12.4 lbf.in (1.4 N.m) screw clamp terminals
|
Height
|
3.5 in (89 mm)
|
Width
|
0.4 in (9.3 mm)
|
Depth
|
2.6 in (66 mm)
|
Product Weight
|
0.11 lb(US) (0.05 kg)
|
Color
|
Dark grey
|