Contact operation
|
Standard
|
[Uc] control circuit voltage
|
24 V AC 50/60 Hz
|
Status LED
|
With
|
Control Type
|
Without push-button
|
[Uimp] rated impulse withstand voltage
|
4 kV 1.2/50 µs IEC 61810-7
|
[Ie] rated operational current
|
5 A AC-1/DC-1) NO IEC
2.5 A AC-1/DC-1) NC IEC
1 A 28 V DC-13) NO
|
Minimum switching capacity
|
25 mW subject to switching frequency, environment or expected reliability level etc
|
Average coil consumption in VA
|
1.2 AC
|
Operating time
|
20 ms between coil de-energisation and making of the Off-delay contact
20 ms between coil energisation and making of the On-delay contact
|
CAD overall width
|
0.8 in (21 mm)
|
CAD overall height
|
1.06 in (27 mm)
|
CAD overall depth
|
1.8 in (46 mm)
|
Minimum switching current
|
5 mA subject to switching frequency, environment or expected reliability level etc
|
Minimum switching voltage
|
5 V subject to switching frequency, environment or expected reliability level etc
|
Rated operational voltage limits
|
19.2...26.4 V AC
|
[Ui] rated insulation voltage
|
250 V IEC
|
Maximum switching voltage
|
250 V AC
28 V DC
|
Drop-out voltage threshold
|
>= 0.15 Uc AC
|
Load current
|
5 A 250 V AC
5 A 28 V DC
|
Maximum switching capacity
|
1250 VA AC
140 W DC
|
Average resistance
|
180 Ohm at 73.4 °F (23 °C) +/- 10 %
|
Mechanical durability
|
10000000 cycles
|
Electrical durability
|
100000 cycles for resistive load
50000 cycles, 1 A at 28 V, DC-13 NO
|
Safety reliability data
|
B10d = 100000
|
Operating rate
|
<= 1200 cycles/hour under load
<= 18000 cycles/hour no-load
|
Utilisation coefficient
|
20 %
|
Dielectric strength
|
2000 V AC between coil and contact with basic insulation
2000 V AC between poles with basic insulation
1000 V AC between contacts with micro disconnection
|
Protection category
|
RT I
|
Pollution degree
|
3
|
Operating position
|
Any position
|
Test levels
|
Level A group mounting
|
Sale per indivisible quantity
|
10
|
Contacts material
|
Silver alloy (Ag/Ni)
|
Net Weight
|
0.073 lb(US) (0.033 kg)
|