Overload current profile
|
300 % Ie for 5 s
|
On-load factor
|
70 %
|
Operating cycles/hour
|
35 cyc/h
|
Minimum motor current
|
20 % Ie
|
Device connection
|
In line
|
[Us] control circuit voltage
|
24 V DC +/- 10 %
|
Control power
|
21.6 W starting and stopping
3 W steady state
|
Integrated motor overload protection
|
False
|
Protection type
|
Phase failure: mains
Thermal protection: starter
Bypass error: starter
Control voltage Us: starter
|
Rated current pwr loss specification
|
45 A
|
Power loss static current independent
|
3 W
|
Power loss per device current dependent
|
9 W
|
Power loss during starting
|
264 W 300 % Ie
|
Standards
|
EN/IEC 60947-4-2
UL 60947-4-2
IEC 60664-1
|
Product certifications
|
CE
UKCA
CCC
RCM
EAC
|
Marking
|
CE
CCC
UKCA
RCM
EAC
|
[Uc] control circuit voltage
|
24 V DC
|
Discrete input number
|
3
|
Discrete input type
|
(DI) digital input, 10 kOhm
(DI2) digital input, 10 kOhm
(BOOST) digital input, 10 kOhm
|
Input compatibility
|
Discrete input level 1 PLC conforming to EN/IEC 61131-2
|
Discrete input logic
|
Digital input at State 0: 0...< 5 V and <= 0.2 mA at State 1: > 13 V, >= 0.5 mA
|
Relay output number
|
1
|
Relay output type
|
Relay outputs R1A, R1C NO
|
Minimum switching current
|
2.5 mA at 24 V DC for relay outputs
|
Maximum switching current
|
On resistive load for relay outputs : 1 A 250 V AC 400000 cycles
On resistive load for relay outputs : 1 A 30 V DC 400000 cycles
On inductive load for relay outputs : 1 A 250 V AC cos phi = 0.4 100000 cycles
On inductive load for relay outputs : 1 A 30 V DC cos phi = 0.4 100000 cycles
|
Discrete output number
|
1
|
Discrete output type
|
Non programmable digital output DQ1 <= 30 V 200 mA
|
Display type
|
1 LED (green) for control power energized
1 LED (yellow and red) for motor operation phases, errors
|
Display screen available
|
False
|
Operating position
|
Vertical +/- 30 degree
|
Height
|
166 mm
|
Width
|
55 mm
|
Depth
|
165 mm
|
Net weight
|
1.3 kg
|
Suitable for mounting onto standard rails
|
True
|
Function available
|
Deceleration voltage ramp
Boost
|
Internal bypass
|
True
|
Material declaration
|
True
|
Pollution degree
|
Level 2
|
Environmental class (during operation)
|
Without salt mist: 3C3 conforming to IEC 60721-3-3
3S3 conforming to IEC 60721-3-3
|
[Uimp] rated impulse withstand voltage
|
4 kV
|
[Ui] rated insulation voltage
|
480 V
|
Electromagnetic compatibility
|
Conducted and radiated emissions level B conforming to IEC 60947-4-2
Short voltage interruptions level 3 conforming to IEC 61000-4-11
Electrostatic discharge level 2 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 1 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 2 conforming to IEC 61000-4-4
Oscillatory waves immunity level 3 conforming to IEC 61000-4-12
Voltage/current impulse level 2 conforming to IEC 61000-4-5
Conducted disturbances, induced by radiofrequency fields level 1 conforming to IEC 61000-4-6
|
Ambient air temperature for operation
|
-10…40 °C (without derating)
40…60 °C (with current derating 1.5 % per °C)
|
Ambient air temperature for storage
|
-25…70 °C
|
Ambient air transport temperature
|
-40…70 °C
|
Operating altitude
|
0...1000 m without derating
1000...4000 m 1 % per 100 m
|
Relative humidity
|
5…95 % non condensing without dripping water conforming to IEC 60068-2-3
|
Maximum acceleration under vibrational stress (during operation)
|
10 m/s² at 9...200 Hz
|
Maximum acceleration under vibratory load (during storage)
|
10 m/s² at 9...200 Hz
|
Maximum acceleration under vibratory load (during transport)
|
10 m/s² at 9...200 Hz
|
Maximum deflection under vibratory load (during operation)
|
3 mm at 2-9 Hz
|
Maximum deflection under vibratory load (during storage)
|
3 mm at 2-9 Hz
|
Maximum deflection under vibratory load (during transport)
|
3 mm at 2-9 Hz
|
Maximum acceleration under shock impact (during operation)
|
100 m/s² at 11 ms
|
Maximum acceleration under shock load (during storage)
|
100 m/s² at 11 ms
|
Maximum acceleration under shock load (during transport)
|
100 m/s² at 11 ms
|
Packaging without single use plastic
|
No
|
Packaging made with recycled cardboard
|
Yes
|
REACh Regulation
|
REACh Declaration
|
REACh free of SVHC
|
Yes
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
|
Toxic heavy metal free
|
Yes
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg CO2 eq, Total Life cycle)
|
181
|