Range of product
|
Altivar Soft Starter ATS480
|
Product or component type
|
Soft starter
|
Product destination
|
Asynchronous motors
|
Product specific application
|
Process and infrastructures
|
Device short name
|
ATS480
|
Network number of phases
|
3 phases
|
Utilisation category
|
AC-3A
AC-53A
|
Ue power supply voltage
|
208...690 V - 15...10 %
|
Power supply frequency
|
50...60 Hz - 20...20 %
|
[Ie] rated operational current
|
Normal duty: 320.0 A (at <40 °C)
|
Rated current in heavy duty
|
250.0 A at 40 °C for heavy duty
|
Torque control
|
True
|
IP degree of protection
|
IP00
|
Motor power kW
|
90.0 kW at 230 V in the motor supply line normal duty
75.0 kW at 230 V in the motor supply line heavy duty
160.0 kW at 400 V in the motor supply line normal duty
132.0 kW at 400 V in the motor supply line heavy duty
160.0 kW at 440 V in the motor supply line normal duty
132.0 kW at 440 V in the motor supply line heavy duty
220.0 kW at 500 V in the motor supply line normal duty
160.0 kW at 500 V in the motor supply line heavy duty
220.0 kW at 525 V in the motor supply line normal duty
160.0 kW at 525 V in the motor supply line heavy duty
250.0 kW at 660 V in the motor supply line normal duty
220.0 kW at 660 V in the motor supply line heavy duty
315.0 kW at 690 V in the motor supply line normal duty
250.0 kW at 690 V in the motor supply line heavy duty
160.0 kW at 230 V to the motor delta terminals normal duty
132.0 kW at 230 V to the motor delta terminals heavy duty
250.0 kW at 400 V to the motor delta terminals normal duty
220.0 kW at 400 V to the motor delta terminals heavy duty
|
Motor power hp
|
100.0 hp at 208 V normal duty
75.0 hp at 208 V heavy duty
125.0 hp at 230 V normal duty
100.0 hp at 230 V heavy duty
250.0 hp at 460 V normal duty
200.0 hp at 460 V heavy duty
300.0 hp at 575 V normal duty
250.0 hp at 575 V heavy duty
|
Option card
|
Communication module for Profibus DP V1
Communication module for Modbus TCP/EtherNet/IP
Communication module for CANopen daisy chain
Communication module for CANopen Sub-D
Communication module for CANopen open style
|
Device connection
|
In the motor supply line
To the motor delta terminals
|
[Us] control circuit voltage
|
110...230 V AC 50/60 Hz - 15...10 %
|
Apparent power
|
0.106 kVA
|
Integrated motor overload protection
|
True
|
Motor thermal protection class
|
Class 10E
|
Protection type
|
Phase failure: line
Integrated thermal protection: motor
Thermal protection: starter
Current overload: motor
Underload: motor
Excessive starting time, locked rotor: motor
Motor phase loss: motor
Line supply phase loss: line
Line supply phase loss: motor
Thermal protection: motor
|
Current limiting %In (5 x Ie maximum)
|
150…700 %
|
Rated current pwr loss specification
|
320.0 A
|
Power loss static current independent
|
25.0 W
|
Power loss per device current dependent
|
882.0 W
|
Standards
|
IEC 60947-4-2
UL 60947-4-2
IEC 60664-1
|
Product certifications
|
CE
cULus
CCC
UKCA
RCM
EAC
DNV
ABS
BV
CCS
|
Marking
|
CE
CCC
UKCA
EAC
RCM
CULus
|
[Uc] control circuit voltage
|
24 V DC
|
Discrete input number
|
4
|
Discrete input type
|
(STOP) logic inputs, 3500 Ohm
(RUN) logic inputs, 3500 Ohm
(DI3) programmable as logic input, 3500 Ohm
(DI4) programmable as logic input, 3500 Ohm
|
Input compatibility
|
STOP: discrete input level 1 PLC conforming to IEC 61131-2
RUN: discrete input level 1 PLC conforming to IEC 61131-2
DI3: discrete input level 1 PLC conforming to IEC 61131-2
DI4: discrete input level 1 PLC conforming to IEC 61131-2
|
Discrete input logic
|
Programmable digital input at State 0: < 5 V
|
Relay output number
|
3
|
Relay output type
|
Relay outputs R1A 1 NO
Relay outputs R1B 1 NO
Relay outputs RIC NO/NC programmable
|
Minimum switching current
|
100 mA at 12 V DC for relay outputs
|
Maximum switching current
|
Relay outputs 2 A at 250 V AC
Relay outputs 2 A at 30 V DC
Relay outputs
|
Discrete output number
|
2
|
Discrete output type
|
(DQ1) programmable digital output <= 30 V
(DQ2) programmable digital output <= 30 V
|
Output compatibility
|
Open collector level 1 PLC conforming to IEC 65A-68
|
Analogue input number
|
1
|
Analogue input type
|
AI1/PTC PTC/Pt 100 temperature probe
PTC2 PTC/Pt 100 temperature probe
PTC3 PTC/Pt 100 temperature probe
|
Analogue output number
|
1
|
Analogue output type
|
Current output AQ1: 0...20 mA or 0...10 V, impedance <500 Ohm
|
Communication port protocol
|
Modbus serial
|
Connector type
|
1 RJ45
|
Communication data link
|
Serial
|
Physical interface
|
2-wire RS 485
|
Transmission rate
|
1200...256000 bit/s
|
Transmission frame
|
RTU
|
Data format
|
8 bits, configurable odd, even or no parity
|
Type of polarization
|
No impedance for Modbus serial
|
Number of addresses
|
0…227 for Modbus serial
|
Method of access
|
Slave Modbus serial
|
Function available
|
External bypass control
Pre-heating
Smoke extraction
Multi-motor cascade
Second motor set
User management
Ports and services hardening
Security event logging
Cybersecure firmware update
Single direction
|
Display screen available
|
True
|
Operating position
|
Vertical +/- 10 degree
|
Height
|
380.0 mm
|
Width
|
320.0 mm
|
Depth
|
277.0 mm
|
Net weight
|
18.2 kg
|
Electromagnetic compatibility
|
Conducted and radiated emissions level A conforming to IEC 60947-4-2
Conducted and radiated emissions with bypass level B conforming to IEC 60947-4-2
Damped oscillating waves level 3 conforming to IEC 61000-4-12
Electrostatic discharge level 3 conforming to IEC 61000-4-11
Immunity to electrical transients level 4 conforming to IEC 61000-4-4
Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
Voltage/current impulse level 3 conforming to IEC 61000-4-5
|
Pollution degree
|
Level 3
|
[Uimp] rated impulse withstand voltage
|
6 kV
|
[Ui] rated insulation voltage
|
690 V
|
Environmental class (during operation)
|
Class 3C3 according to IEC 60721-3-3
Class 3S2 according to IEC 60721-3-3
|
Relative humidity
|
0…95 % without condensation or dripping water conforming to IEC 60068-2-3
|
Ambient air temperature for operation
|
40…60 °C (with current derating of 2 % per °C)
-15…40 °C (without derating)
|
Ambient air temperature for storage
|
-25…70 °C
|
Operating altitude
|
<= 1000 m without derating
> 1000...4000 m with current derating 1 % per 100 m
|
Maximum deflection under vibratory load (during operation)
|
1.5 mm at 2...13 Hz
|
Maximum deflection under vibratory load (during storage)
|
1.75 mm at 2...9 Hz
|
Maximum deflection under vibratory load (during transport)
|
1.75 mm at 2...9 Hz
|
Maximum acceleration under vibrational stress (during operation)
|
10 m/s² at 13...200 Hz
|
Maximum acceleration under vibratory load (during storage)
|
15 m/s² at 200...500 Hz
10 m/s² at 9...200 Hz
|
Maximum acceleration under vibratory load (during transport)
|
15 m/s² at 200...500 Hz
10 m/s² at 9...200 Hz
|
Maximum acceleration under shock impact (during operation)
|
150 m/s² at 11 ms
|
Maximum acceleration under shock load (during storage)
|
100 m/s² at 11 ms
|
Maximum acceleration under shock load (during transport)
|
100 m/s² at 11 ms
|
Packaging without single use plastic
|
No
|
Packaging made with recycled cardboard
|
Yes
|
SCIP Number
|
D66ceea4-b4bd-43a8-ad98-b5f042f3961e
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg CO2 eq, Total Life cycle)
|
22489
|