Device application
|
Building
|
Maximum power consumption in W
|
0.5 W standby
|
Maximum switching current
|
10 A - 250 V AC pf = 0.6
16 A - 250 V AC pf = 1
|
Minimum switching current
|
10 mA 230 V AC
100 mA 24 V AC/DC
|
[Ue] rated operational voltage
|
230 V AC +10 % -15 % at 50/60 Hz
|
Contacts type and composition
|
C/O
|
Control type
|
By calculation of sunrise/sunset times
|
Control button type
|
4 push-buttons
|
Function available
|
External input for override
Code lock function
Holiday schedules
Automatic winter/summer time changeover
On/off permanent switching
Sunrise/sunset time offset +/- 120 min
Position setting
Switch preselection
|
Load type
|
Incandescent lamp 2600 W
Halogen lamp 2600 W
Non-corrected fluorescent tube 2300 VA
Serial-compensated fluorescent tube 2300 VA
Parallel compensated fluorescent lamp 730 VA 80 µF
Compact fluorescent lamp 170 W
LED lamp < 2 W 30 W
LED lamp > 2 W 200 W
|
Accuracy
|
+/- 0.25 s/day 25 °C
|
Output type
|
Dry contact
|
Operating mode
|
Evening on, morning off
Evening off, morning on inactive
Only timer switch is active
|
Maximum number of switchings
|
84
|
Backup time
|
10 years
|
Display type
|
Backlit LCD
|
Information displayed
|
Time
Operating time counter (per channel)
Switching behaviour
Day
|
Mounting support
|
TH35 DIN rail conforming to EN 60715
|
Connections - terminals
|
2 x 0.5…2.5 mm² screw terminals solid or flexible
1 x 2.5 mm² screw terminals solid or flexible with sleeve
|
Marking
|
CE
|
Electrical insulation class
|
Class II
|
Overvoltage category
|
Class 3
|
Height
|
92.6 mm
|
Width
|
45 mm
|
Depth
|
66.7 mm
|
Net weight
|