Network frequency
|
50...60 Hz
|
Mounting support
|
Rail
|
Tripping threshold
|
5...50 A
|
Electromagnetic compatibility
|
Resistance to electrostatic discharge: 8 kV in open air conforming to IEC 61000-4-2
Resistance to electrostatic discharge: 6 kV in direct mode conforming to IEC 61000-4-2
Conducted emission: class A conforming to EN 55011
Immunity to electromagnetic interference: 10 V/m conforming to IEC 61000-4-3
Immunity to fast transients: 2 kV conforming to IEC 61000-4-4
Surge withstand: 6 kV conforming to IEC 61000-4-5
Conducted HF disturbances: 10 V conforming to IEC 61000-4-6
|
Auxiliary contact composition
|
1 NO + 1 NC
|
[Ith] conventional free air thermal current
|
3 A for signalling circuit
|
Associated fuse rating
|
3 A gG for signalling circuit
3 A BS for signalling circuit
|
[Uimp] rated impulse withstand voltage
|
6 kV
|
Time range
|
1...120 s - control type R-time
0.3...30 s - control type O-time
|
Local signalling
|
1 LED (green)
1 LED (red)
|
Control type
|
Automatic: reset
|
Connections - terminals
|
Signalling circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end
Signalling circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible without cable end
Signalling circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Signalling circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable end
|
Tightening torque
|
Signalling circuit: 1.7 N.m M3.5
|
Height
|
70.3 mm
|
Width
|
71 mm
|
Depth
|
77.2 mm
|
Net weight
|
0.192 kg
|