LTMR100PFM
Motor controller, TeSys T, Motor Management, Profibus DP, 6 logic inputs, 3 logic outputs, 5 to 100A, 100 to 240VAC
|
|
|
Main
Range
|
TeSys
|
Product name
|
TeSys T
|
Device short name
|
LTMR
|
Product or component type
|
Motor controller
|
Device application
|
Equipment monitoring and control
|
Measurement current
|
5…100 A
|
[Us] rated supply voltage
|
100...240 V AC 50/60 Hz
|
Current consumption
|
8...62.8 mA
|
Supply voltage limits
|
93.5…264 V AC
|
Communication port protocol
|
Profibus DP
|
Bus type
|
Profibus DP polarised 2-wire RS485 interface, addressing 1...125, transmission rate 9.6 kbit/s...12 Mbit/s, SUB-D 9 with 2 shielded twisted pairs, type A
Profibus DP polarised 2-wire RS485 interface, addressing 1...125, transmission rate 9.6 kbit/s...12 Mbit/s, terminal block with 2 shielded twisted pairs, type A
|
Complementary
[Ui] rated insulation voltage
|
690 V conforming to EN/IEC 60947-1
690 V conforming to CSA C22.2 No 14
690 V conforming to UL 508
|
[Uimp] rated impulse withstand voltage
|
4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1
6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1
0.8 kV communication circuit conforming to EN/IEC 60947-4-1
|
Short-circuit withstand
|
100 kA conforming to EN/IEC 60947-4-1
|
Associated fuse rating
|
4 A gG for output
0.5 A gG for control circuit
|
Protection type
|
Thermal overload protection
Power factor variation
Overload
Locked rotor
Thermal protection
Reverse polarity protection
Phase unbalance
Earth-leakage protection
Phase failure
Load fluctuation
Overload (long time)
|
Network and machine diagnosis type
|
Starting current and time
Trip history information
Running hours counter/operating time
Phase fault and earth fault trip counters
Trip context information
Event recording
Remaining operating time before overload tripping
Motor control command recording
Waiting time after overload tripping
Fault recording
|
Logic input number
|
6
|
Input current
|
3.1 mA at 100 V
7.5 mA at 240 V
|
Current state 0 guaranteed
|
Logic input: 0...40 V and <= 15 mA for 25 ms
|
Current state 1 guaranteed
|
Logic input: 79...264 V and >= 2 mA for 25 ms
|
Maximum output switching frequency
|
2 Hz
|
Load current
|
5 A at 250 V AC for logic output
5 A at 30 V DC for logic output
|
Permissible power
|
480 VA (AC-15), Ie = 2 A, 500000 cycles (output)
30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)
|
Maximum operating rate
|
1800 cyc/h
|
Contacts type and composition
|
1 NO + 1 NC fault signal
3 NO
|
Metering type
|
Earth-fault current
Phase current I1, I2, I3 RMS
Temperature
Imbalance current
Average current Iavg
|
Measurement accuracy
|
5...15 % earth fault current internal measurement
1 % voltage (100...830 V)
3 % power factor
5 % earth fault current external measurement
+/- 30 min/year internal clock
0,02 temperature
5 % active and reactive power
0,02 current
|
Overvoltage category
|
III
|
Connection pitch
|
5.08 mm
|
Connections - terminals
|
Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible with cable end
Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) solid without cable end
Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) flexible with cable end
Control circuit: connector 2 cable(s) 0.2…1.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 2 cable(s) 0.5…1.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) solid without cable end
|
Tightening torque
|
Control circuit: 0.5…0.6 N.m flat screwdriver 3 mm
|
Pollution degree
|
3
|
Electromagnetic compatibility
|
Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2
Radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3
Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4
Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4
Voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11
Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6
Temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5
Temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5
Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
Relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5
Relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5
Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
|
Width
|
91 mm
|
Height
|
61 mm
|
Depth
|
122.5 mm
|
Net weight
|
0.53 kg
|
Web services
|
Web server
|
Compatibility code
|
LTMR
|
Environment
Standards
|
EN 60947-4-1
IACS E10
CSA C22.2 No 14
UL 508
IEC 60947-4-1
|
Product certifications
|
KERI
RMRoS
ABS
UL
ATEX
NOM
RINA
BV
CCC
GL
DNV
CSA
LROS (Lloyds register of shipping)
EAC
C-Tick
|
Protective treatment
|
12 x 24 hour cycles conforming to EN/IEC 60068-2-30
48 h conforming to EN/IEC 60070-2-11
TH conforming to EN/IEC 60068
|
Fire resistance
|
650 °C conforming to EN/IEC 60695-2-12
960 °C conforming to UL 94
|
Ambient air temperature for operation
|
-20…60 °C
|
Ambient air temperature for storage
|
-40…80 °C
|
Operating altitude
|
<= 2000 m without derating
|
Mechanical robustness
|
Vibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6
Vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6
Shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27
|
IP degree of protection
|
IP20
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
10.000 cm
|
Package 1 Width
|
7.200 cm
|
Package 1 Length
|
13.500 cm
|
Package 1 Weight
|
530.000 g
|
Unit Type of Package 2
|
S02
|
Number of Units in Package 2
|
10
|
Package 2 Height
|
15.000 cm
|
Package 2 Width
|
30.000 cm
|
Package 2 Length
|
40.000 cm
|
Package 2 Weight
|
5.649 kg
|
Offer Sustainability
Packaging without single use plastic
|
Yes
|
Packaging made with recycled cardboard
|
Yes
|
SCIP Number
|
Fc01c523-9a07-4dfa-988f-c721d4816782
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Compliant with Exemptions
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
PVC free
|
Yes
|
Halogen content performance
|
Halogen free plastic parts product
|
Take-back
|
No
|
Contractual warranty
|
|