Contacts type and composition
|
1 C/O timed contact
1 C/O timed or instantaneous contact
|
Time delay type
|
Pulse delay
Safe-guard
Bistable
Interval
|
Time delay range
|
0.1...1 s
1...10 h
1...10 s
6...60 min
10...100 h
6...60 s
1...10 min
|
Control type
|
Rotary knob front panel
|
[Us] rated supply voltage
|
24...240 V AC
24 V DC
|
Voltage range
|
0.85...1.1 Us
|
Supply frequency
|
50...60 Hz +/- 5 %
|
Connections - terminals
|
Screw terminals, 2 x 1.5 mm² with cable end
Screw terminals, 2 x 2.5 mm² without cable end
|
Tightening torque
|
0.6…1 N.m conforming to IEC 60947-1
|
Housing material
|
Self-extinguishing
|
Repeat accuracy
|
+/- 0.5 % conforming to IEC 61812-1
|
Temperature drift
|
+/- 0.05 %/°C
|
Voltage drift
|
+/- 0.2 %/V
|
Setting accuracy of time delay
|
+/- 10 % of full scale at 25 °C conforming to IEC 61812-1
|
Time delay type
|
Pulse delay - Ad- Pulse delayed relay w/ control signal
Pulse delay - Ah- Pulse delayed relay (single cycle) w/ control signal
Safe-guard - N- Safe-guard relay
Safe-guard - O- Delayed Safe-guard relay
Pulse delay - P- Pulse delayed relay w/ fixed pulse length
Pulse delay - Pt- Pulse delayed relay w/ fixed pulse length and pause/summation
Bistable - TI- Bistable relay w/ control signal on
Bistable - Tt- Retriggerable bistable relay w/ control signal on
Interval - W- Interval relay w/ control signal off
|
Control signal pulse width
|
30 ms
100 ms under load
|
Insulation resistance
|
100 MOhm at 500 V DC conforming to IEC 60664-1
|
Recovery time
|
120 ms on de-energisation
|
Immunity to microbreaks
|
10 ms
|
Power consumption in VA
|
50 VA at 240 V AC
|
Power consumption in W
|
0.7 W at 24 V DC
|
Breaking capacity
|
2000 VA
|
Minimum switching current
|
10 mA at 5 V
|
Maximum switching current
|
8 mA
|
Maximum switching voltage
|
250 V
|
Electrical durability
|
100000 cycles for resistive load, 8 A at 250 V, AC
|
Mechanical durability
|
10000000 cycles
|
Rated impulse withstand voltage
|
5 kV for 1.2…50 µs conforming to IEC 60664-1
5 kV conforming to IEC 61812-1
|
Power on delay
|
100 ms
|
Safety reliability data
|
B10d = 170000
MTTFd = 182.6 years
|
Mounting position
|
Any position in relation to normal vertical mounting plane
|
Mounting support
|
35 mm DIN rail conforming to IEC 60715
|
Status LED
|
LED green (flashing) for timing in progress
LED green (steady) for power ON
LED yellow for relay energised
|
Function available
|
Ad- Pulse delayed relay w/ control signal-2 C/O
Ah- Pulse delayed relay (single cycle) w/ control signal-2 C/O
N- Safe-guard relay-2 C/O
O- Delayed Safe-guard relay-2 C/O
P- Pulse delayed relay w/ fixed pulse length-2 C/O
Pt- Pulse delayed relay w/ fixed pulse length and pause/summation-2 C/O
TI- Bistable relay w/ control signal on-2 C/O
Tt- Retriggerable bistable relay w/ control signal on-2 C/O
W- Interval relay w/ control signal off-2 C/O
|
Width
|
22.5 mm
|
Net weight
|
0.09 kg
|
Control type
|
With test button
|
Number of functions
|
9
|
Dielectric strength
|
2.5 kV for 1 mA/1 minute at 50 Hz conforming to IEC 61812-1
|
Standards
|
IEC 61812-1
IEC 61000-6-1
IEC 61000-6-3
IEC 61000-6-4
IEC 61000-6-2
|
Directives
|
2006/95/EC - low voltage directive
2004/108/EC - electromagnetic compatibility
|
Product certifications
|
CSA
CCC
GL
cULus
EAC
CE
RCM
|
Ambient air temperature for operation
|
-20…60 °C
|
Ambient air temperature for storage
|
-30…60 °C
|
IP degree of protection
|
IP40 housing: conforming to IEC 60529
IP50 front face: conforming to IEC 60529
IP20 terminal block: conforming to IEC 60529
|
Vibration resistance
|
20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6
|
Shock resistance
|
15 gn for 11 ms conforming to IEC 60068-2-27
|
Relative humidity
|
93 %, without condensation conforming to IEC 60068-2-30
|
Electromagnetic compatibility
|
Electrostatic discharge immunity test - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2
Electrostatic discharge immunity test - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Fast transients immunity test - test level: 1 kV level 3 (capacitive connecting clip) conforming to IEC 61000-4-4
Fast transients immunity test - test level: 2 kV level 3 (direct contact) conforming to IEC 61000-4-4
Surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5
Surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5
Radiated radio-frequency electromagnetic field immunity test - test level: 10 V level 3 (0.15...80 MHz) conforming to IEC 61000-4-6
Electromagnetic field immunity test - test level: 10 V/m level 3 (80 MHz...1 GHz) conforming to IEC 61000-4-3
Immunity to microbreaks and voltage drops - test level: 30 % (500 ms) conforming to IEC 61000-4-11
Immunity to microbreaks and voltage drops - test level: 100 % (20 ms) conforming to IEC 61000-4-11
|
Packaging without single use plastic
|
Yes
|
Packaging made with recycled cardboard
|
Yes
|
SCIP Number
|
7bdc2711-0ad2-427c-8ece-532c5e9f09d7
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
|
Mercury free
|
Yes
|
Sustainable packaging
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg CO2 eq, Total Life cycle)
|
54
|