NFC operating frequency
|
13.56 MHz
|
Maximum RF power transmitted
|
0.0002 mW
|
Reset time
|
1500 ms at maximum voltage
|
Maximum switching voltage
|
250 V AC
|
Minimum switching current
|
100 mA at 6 V
|
Maximum switching current
|
8 A AC
|
Supply voltage limits
|
166.4…576 V AC line to line
96…332.4 V AC line to neutral
|
Power consumption in VA
|
4 VA at 480 V AC 60 Hz
|
On-load factor
|
100 %
|
Supply voltage frequency
|
50...60 Hz +/- 10 %
|
Output contacts
|
2 C/O
|
Measurement range
|
208...480 V AC
|
Setting accuracy of the switching threshold
|
+/- (1.5 % + 1 V)
|
Setting accuracy of time delay
|
+/- 3 % for 10 s...60 min time delay range
+/- 300 ms for 0...10 s time delay range
|
Hysteresis
|
3 % of fixed for phase failure detection
|
Alarm threshold
|
166...576 V adjustable overvoltage and undervoltage detection (line to line)
96...332 V adjustable overvoltage and undervoltage detection (line to neutral)
5...150 V adjustable asymmetry
45...66 Hz adjustable overfrequency or underfrequency
|
Run-up delay at power-up max
|
650 ms
|
Maximum measuring cycle
|
150 ms measurement cycle as true rms value
|
Threshold adjustment voltage
|
2...20 % of Un selected
|
Adjustment of asymmetry threshold
|
2...20 % of Un selected
|
Repeat accuracy
|
+/- 0.5 % for input circuit
+/- 3 % for time delay
|
Setting accuracy of the switching threshold
|
+/- (1.5 % + 1 V)
|
Measurement error
|
< 0.05 %/Hz with frequency variation
< 0.05 %/°C with temperature variation
|
Response time
|
<= 300 ms
|
Insulation resistance
|
> 100 MOhm at 500 V DC conforming to IEC 60255-27
|
[Ui] rated insulation voltage
|
400 V
|
[Uimp] rated impulse withstand voltage
|
4 kV during 1.2/50 µs
|
Dielectric test voltage
|
2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27
|
Mounting position
|
Any position
|
Connections - terminals
|
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 2 x 0.5...2 x 1.5 mm² (AWG 20...AWG 16) flexible with cable end
Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
Screw terminals, 1 x 0.5...1 x 2.5 mm² (AWG 20...AWG 14) flexible with cable end
|
Tightening torque
|
0.6…1 N.m conforming to IEC 60947-1
0.6…1.0 N.m conforming to IEC 60947-1
|
Housing material
|
Self-extinguishing plastic
|
Local signalling
|
LED Un: (steady), green for power ON
LED R1: (steady), amber for relay energised
LED R1: (blinking), amber for timing in progress
LED R2: (steady), amber for relay energised
LED R2: (blinking), amber for timing in progress
LED PL: (steady), red for alarm phase failure triggered
LED PS: (blinking), red for alarm phase sequence failure triggered
LED UV: (steady), red for alarm undervoltage failure triggered
LED OV: (blinking), red for alarm overvoltage failure triggered
LED UF: (steady), red for alarm underfrequency failure triggered
LED OF: (blinking), red for alarm overfrequency failure triggered
LED ASYM: (steady), red for alarm asymmentry failure triggered
|
Mounting support
|
35 mm DIN rail conforming to IEC 60715
|
Electrical durability
|
100000 cycles
|
Mechanical durability
|
10000000 cycles
|
Utilisation category
|
AC-15 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
AC-1 conforming to IEC 60947-4-1
DC-1 conforming to IEC 60947-4-1
|
[Ith] conventional free air thermal current
|
8 A
|
[Un] rated nominal voltage
|
208...480 V AC 50/60 Hz, non self-powered
120...277 V AC 50/60 Hz, non self-powered
|
Operating system
|
Androidversion >= V7.0
IOSversion >= V14.5
|
Contacts material
|
Cadmium free
|
Control type
|
Without test button
|
Width
|
22.5 mm
|
Height
|
90 mm
|
Depth
|
99 mm
|
Contacts type and composition
|
2 C/O
|
Net weight
|
0.125 kg
|
Immunity to microbreaks
|
10 ms
|
Electromagnetic compatibility
|
Voltage dips and interruptions immunity test - test level: 70 % (25/30 cycles) conforming to IEC 61000-4-11
Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 conforming to IEC 61000-4-3
Immunity for industrial environments conforming to IEC 61000-6-2
1 MHz damped oscillating wave - test level: 2.5 kV CM, 1 kV DM criteria B conforming to IEC 61000-4-18
Voltage dips and interruptions immunity test - test level: 0 % (0.5...25 cycles) conforming to IEC 61000-4-11
Magnetic field at power frequency - test level: 30 A/m (continuous)-300 A/m (1-3 s) level 4 conforming to IEC 61000-4-8
Surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5
Immunity for residential, commercial and light-industrial environments conforming to IEC 61000-6-1
Voltage dips and interruptions immunity test - test level: 40 % (10/12 cycles) conforming to IEC 61000-4-11
Voltage interruptions - test level: 0 % criteria C (250/300 cycles) conforming to IEC 61000-4-29
Electrical fast transient/burst immunity test - test level: 4 kV criteria B (direct) conforming to IEC 61000-4-4
Emission standard for industrial environments conforming to IEC 61000-6-4
Surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5
Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Conducted RF disturbances level 3 conforming to IEC 61000-4-6
|
Standards
|
IEC 60255-1
|
Product certifications
|
CE
UL
CSA
CCC
EAC
RCM
|
Directives
|
2014/30/EU - electromagnetic compatibility
2014/35/EU - low voltage directive
2014/53/EU - radio equipment directive
|
Ambient air temperature for storage
|
-40…70 °C
|
Ambient air temperature for operation
|
-20…60 °C
|
Relative humidity
|
93…97 % at 25…55 °C conforming to IEC 60068-2-30
|
Vibration resistance
|
0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6
1 gn (f= 58.1…150 Hz) not in operation conforming to IEC 60068-2-6
0.035 mm (f= 10…58.1 Hz) in operation conforming to IEC 60068-2-6
0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6
|
Shock resistance
|
15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27
5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27
|
IP degree of protection
|
IP20 (terminals) conforming to IEC 60529
IP40 (housing) conforming to IEC 60529
IP40 (front panel) conforming to IEC 60529
|
Pollution degree
|
3 conforming to IEC 60664-1
3 conforming to UL 508
|
Overvoltage category
|
III conforming to IEC 60664-1
III conforming to UL 508
|
Packaging without single use plastic
|
Yes
|
Packaging made with recycled cardboard
|
Yes
|
SCIP Number
|
5e3fdf99-611b-4d07-ad17-6eba84ab488b
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
|
Mercury free
|
Yes
|
Sustainable packaging
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg CO2 eq, Total Life cycle)
|
58
|