Schneider-Electric
 
TM3TM3 picture- scope
TM3TM3
analog IO module, Modicon TM3, 2 analog or temperature inputs, 1 analog output, screw, 24V DC
Schneider Electric
Characteristics
Main
Range of product Modicon TM3
Product or component type Input/output analog module
Range compatibility Modicon M221
Modicon M241
Modicon M251
Modicon M262
Analogue input number 2
Analogue input type Current 4...20 mA
Current 0...20 mA
Voltage 0...10 V
Voltage - 10...10 V
Thermocouple - 200...1000 °C with thermocouple J
Thermocouple - 200...1300 °C with thermocouple K
Thermocouple 0...1760 °C with thermocouple R
Thermocouple 0...1760 °C with thermocouple S
Thermocouple 0...1820 °C with thermocouple B
Thermocouple - 200...400 °C with thermocouple T
Thermocouple - 200...1300 °C with thermocouple N
Thermocouple - 200...800 °C with thermocouple E
Thermocouple 0...2315 °C with thermocouple C
Ni 100/Ni 1000 temperature probe - 60...180 °C
Pt 100 temperature probe - 200...850 °C
Pt 1000 temperature probe - 200...600 °C
Analogue output number 1
Analogue output type Current: 4...20 mA
Current: 0...20 mA
Voltage: 0...10 V
Voltage: - 10...10 V
Complementary
Analogue input resolution 16 bits
15 bits + sign
Permissible continuous overload 13 V, analogue input type: voltage
40 mA, analogue input type: current
Input impedance <= 50 Ohm current
>= 1 MOhm voltage
>= 1 MOhm thermocouple
>= 1 MOhm temperature probe
Analogue output resolution 12 bits
LSB value 0.15 mV 0...10 Vvoltage
0.30 mV - 10...10 Vvoltage
0.30 µA 0...20 mAcurrent
0.244 µA 4...20 mAcurrent
0.1 °Ctemperature probe
0.1 °Cthermocouple
2.44 mV 0...10 V voltage
4.88 mV - 10...10 V voltage
4.88 µA 0...20 mA current
3.91 µA 4...20 mA current
Load type Resistive
Load impedance ohmic 1 kOhm voltage
300 Ohm current
Stabilisation time 1 ms
Conversion time 100 ms + 100 ms per channel + 1 controller cycle time for analogue input thermocouple
100 ms + 100 ms per channel + 1 controller cycle time for analogue input temperature probe
10 ms + 10 ms per channel + 1 controller cycle time for analogue input voltage/current
Sampling duration 10 ms, analogue input type: voltage/current
100 ms, analogue input type: voltage/current
100 ms, analogue input type: thermocouple
100 ms, analogue input type: temperature probe
Absolute accuracy error +/- 6 °C at 25 °C for thermocouple R, S 0...200 °C
+/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C
+/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C
+/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C
+/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C
+/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C
+/- 0.1 % of full scale at 25 °C for analogue input voltage/current
+/- 0.1 % of full scale at 25 °C for thermocouple C 0...2315 °C
+/- 0.1 % of full scale at 25 °C for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe
+/- 0.1 % of full scale at 25 °C for thermocouple R, S 200...1760 °C
+/- 0.1 % of full scale at 25 °C for thermocouple B 300...1820 °C
+/- 0.1 % of full scale at 25 °C for thermocouple K 0...1300 °C
+/- 0.1 % of full scale at 25 °C for thermocouple J 0...1000 °C
+/- 0.1 % of full scale at 25 °C for thermocouple E 0...800 °C
+/- 0.1 % of full scale at 25 °C for thermocouple T 0...400 °C
+/- 0.1 % of full scale at 25 °C for thermocouple N 0...1300 °C
+/- 0.1 % of full scale at 25 °C for analogue output voltage/current
Temperature drift +/- 0.006 %FS/°C
Repeat accuracy +/-0.5 %FS for input
+/- 0.4 %FS for output
Non-linearity +/- 0.01 %FS, analogue output type: analog output
+/- 0.1 %FS, analogue input type: analog input
Output ripple 20 mV
Cross talk <= 1 LSB
[Us] rated supply voltage 24 V DC
Supply voltage limits 20.4…28.8 V
Type of cable Twisted shielded pairs cable <30 m for input/output circuit
Current consumption 55 mA at 24 V DC via external supply no load
55 mA at 5 V DC via bus connector no load
60 mA at 5 V DC via bus connector full load
80 mA at 24 V DC via external supply full load
Local signalling 1 LED (green) for PWR
Electrical connection 11 x 2.5 mm² removable screw terminal block with pitch 5.08 mm adjustment for inputs, outputs and supply
Insulation Between input and supply at 1500 V AC
Between input and internal logic at 500 V AC
Between output and supply at 1500 V AC
Between output and internal logic at 500 V AC
Marking CE
Surge withstand 1 kV power supply common mode conforming to IEC 61000-4-5
0.5 kV power supply differential mode conforming to IEC 61000-4-5
1 kV I/O common mode conforming to IEC 61000-4-5
0.5 kV I/O differential mode conforming to IEC 61000-4-5
Mounting support Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
Plate or panel with fixing kit
Height 90 mm
Depth 70 mm
Width 23.6 mm
Net weight 0.115 kg
Environment
Standards IEC 61131-2
Product certifications CE
UKCA
RCM
EAC
cULus
cULus HazLoc
Resistance to electrostatic discharge 8 kV in air conforming to IEC 61000-4-2
4 kV on contact conforming to IEC 61000-4-2
Resistance to electromagnetic fields 10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3
1 V/m 2 GHz...3 GHz conforming to IEC 61000-4-3
Resistance to magnetic fields 30 A/m conforming to IEC 61000-4-8
Resistance to fast transients 1 kV (I/O) conforming to IEC 61000-4-4
Resistance to conducted disturbances 10 V 0.15...80 MHz conforming to IEC 61000-4-6
3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to IEC 55011
Immunity to microbreaks 10 ms
Ambient air temperature for operation -10…55 °C horizontal installation
-10…35 °C vertical installation
Ambient air temperature for storage -25…70 °C
Relative humidity 10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
IP degree of protection IP20
Pollution degree 2
Operating altitude 0...2000 m
Storage altitude 0…3000 m
Vibration resistance 3.5 mm at 5…8.4 Hz on DIN rail
3 gn at 8.4…150 Hz on DIN rail
Shock resistance 15 gn for 11 ms
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 7.611 cm
Package 1 Width 10.688 cm
Package 1 Length 12.753 cm
Package 1 Weight 220.0 g
Unit Type of Package 2 S04
Number of Units in Package 2 42
Package 2 Height 30 cm
Package 2 Width 40 cm
Package 2 Length 60 cm
Package 2 Weight 10.421 kg
Unit Type of Package 3 P12
Number of Units in Package 3 504
Package 3 Height 105 cm
Package 3 Width 120 cm
Package 3 Length 80 cm
Package 3 Weight 130 kg
Offer Sustainability
Packaging without single use plastic Yes
Packaging made with recycled cardboard No
REACh Regulation
print REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
print EU RoHS Declaration
Toxic heavy metal free Yes
Mercury free Yes
RoHS exemption information
print Yes
China RoHS Regulation
print China RoHS declaration
Environmental Disclosure
print Product Environmental Profile
Circularity Profile
print End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
PVC free Yes
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Take-back No
Carbon footprint (kg CO2 eq, Total Life cycle) 99