Current consumption
|
5 mA at 5 V DC via bus connector at state on
35 mA at 5 V DC via bus connector at state off
0 mA at 24 V DC via bus connector at state on
10 mA at 24 V DC via bus connector at state off
1200 mA at 24 V DC external power supply at state on
|
Input voltage limits
|
19.2...28.8 V per input
|
Input current limits
|
5 mA per input
|
Response time
|
< 10 ms turn-on for input
< 10 ms turn-off for input
|
Output voltage
|
24 V DC for transistor output
|
Maximum load current
|
800 mA per channel in starting mode during 100 ms
300 mA per channel in normal mode
|
Insulation
|
Between the RJ45 connectors and internal logic at 500 V AC
Non-insulated between RJ45 connectors
|
Output protection type
|
Against overload, protection technology: current limiter
|
Reset
|
Automatic reset
|
Local signalling
|
3 LEDs green for input status per channel
2 LEDs green for output status per channel
|
Electrical connection
|
3 x 2.5 mm² removable screw terminal block with pitch 5.08 mm adjustment for connecting the 24 V DC power supply
4 RJ45 connectorsfor connecting the motor starters
|
Mounting support
|
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
Plate or panel with fixing kit
|
Height
|
90 mm
|
Depth
|
85 mm
|
Width
|
30 mm
|
Net weight
|
0.115 kg
|
Product certifications
|
CE
cULus
UKCA
RCM
EAC
|
Marking
|
CE
|
Resistance to electrostatic discharge
|
8 kV in air conforming to EN/IEC 61000-4-2
4 kV on contact conforming to EN/IEC 61000-4-2
|
Resistance to electromagnetic fields
|
10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
1 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3
|
Resistance to magnetic fields
|
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
|
Resistance to fast transients
|
1 kV for input conforming to EN/IEC 61000-4-4
1 kV for output conforming to EN/IEC 61000-4-4
|
Surge withstand
|
1 kV input common mode conforming to EN/IEC 61000-4-5
1 kV output common mode conforming to EN/IEC 61000-4-5
|
Resistance to conducted disturbances
|
10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6
3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
|
Electromagnetic emission
|
Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to EN/IEC 55011
|
Ambient air temperature for operation
|
-10…35 °C vertical installation
-10…55 °C horizontal installation
|
Ambient air temperature for storage
|
-25…70 °C
|
Relative humidity
|
10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
|
IP degree of protection
|
IP20 with protective cover in place
|
Pollution degree
|
2
|
Operating altitude
|
0...2000 m
|
Storage altitude
|
0…3000 m
|
Vibration resistance
|
3.5 mm at 5…8.4 Hz on DIN rail
3 gn at 8.4…150 Hz on DIN rail
3.5 mm at 5…8.4 Hz on panel
3 gn at 8.4…150 Hz on panel
|
Shock resistance
|
15 gn for 11 ms
|
Packaging without single use plastic
|
Yes
|
Packaging made with recycled cardboard
|
No
|
SCIP Number
|
91cf81c4-f22d-428b-a036-2e24fcc66509
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
|
Toxic heavy metal free
|
Yes
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
PVC free
|
Yes
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg CO2 eq, Total Life cycle)
|
134
|