TPRPM038
Power module, TeSys island, 40A AC-1, 38A AC-3, 18.5kW, 20hp
|
|
|
Main
Range of product
|
TeSys
|
Product name
|
TeSys island
|
Device short name
|
TPRPM
|
Product or component type
|
Power module
|
Device presentation
|
Power module connected to an automation controller through a bus coupler
Operational only when connected to a bus coupler
|
Function available
|
Upstream voltage presence detection
Electronic thermal overload protection
Monitoring of currents
Control of third party power devices when associated to TPRDG IO module
|
Product compatibility
|
TPRBC bus coupler
TPRDG digital IO module
TPRAN analog IO module
|
Poles description
|
3P
|
Motor power kW
|
9 kW at 230 V AC 50 Hz
18.5 kW at 380...415 V AC 50 Hz
18.5 kW at 440 V AC 50 Hz
18.5 kW at 500 V AC 50 Hz
18.5 kW at 690 V AC 50 Hz
|
Motor power HP (UL / CSA)
|
2 hp at 120 V AC 60 Hz for 1 phase motors
5 hp at 240 V AC 60 Hz for 1 phase motors
10 hp at 208 V AC 60 Hz for 3 phases motors
10 hp at 240 V AC 60 Hz for 3 phases motors
20 hp at 480 V AC 60 Hz for 3 phases motors
25 hp at 600 V AC 60 Hz for 3 phases motors
|
[Ue] rated operational voltage
|
<= 690 V AC 47...63 Hz
|
[Ie] rated operational current
|
38 A (at <50 °C) at <= 440 V AC-3
40 A (at <50 °C) at <= 440 V AC-1
40 A (at <50 °C) AC-3e
|
[Ith] conventional free air thermal current
|
40 A (at 50 °C)
|
[Ui] rated insulation voltage
|
690 V conforming to IEC 60947-4-1
600 V conforming to UL 60947-4-1
600 V conforming to CSA C22.2 No 60947-4-1
|
[Uimp] rated impulse withstand voltage
|
6 kV
|
Overvoltage category
|
III
|
Thermal protection adjustment range
|
0.76…38 A
|
Thermal overload class
|
Class 5…30
|
Reset
|
Remotely or automatically
|
[Uc] control circuit voltage
|
24 V DC supplied by the bus coupler
|
Current consumption
|
60 mA
|
Power dissipation in W
|
0.9 W at Ie AC-3
|
Complementary
Protection type
|
Thermal overload protection
Motor overheat
Overcurrent
Undercurrent
Jam
Long start
Stall
Rapid cycle lockout
Phase loss
Rapid restart lockout
Phase reversal
Phase sequence
Phase unbalance
Ground current
|
Monitoring type
|
Time device ON
Number of faults
Number of device power cycles
Average current Iavg
Average voltage Vavg
Max current Imax
Max voltage Vmax
|
Local signalling
|
1 LED (green/red) for DS (device status)
1 LED (green/red) for LS (load status)
|
Standards
|
EN/IEC 60947-1
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
|
Product certifications
|
EAC
CCC
CSA
UL
|
Mounting mode
|
Horizontal and vertical (35 mm symmetrical DIN rail)
|
Connections - terminals
|
Screw-clamp terminals 1 cable(s) 1.5…10 mm² (AWG 16...AWG 8) rigid
Screw-clamp terminals 2 cable(s) 1.5…10 mm² (AWG 16...AWG 8) rigid
Screw-clamp terminals 1 cable(s) 2.5…10 mm² (AWG 14...AWG 8) flexible without cable end
Screw-clamp terminals 2 cable(s) 2.5…10 mm² (AWG 14...AWG 8) flexible without cable end
Screw-clamp terminals 1 cable(s) 1.5…10 mm² (AWG 16...AWG 10) flexible with cable end
Screw-clamp terminals 2 cable(s) 1.5…6 mm² (AWG 16...AWG 10) flexible with cable end
|
Tightening torque
|
2.5 N.m - with screwdriver flat Ø 6 mm
2.5 N.m - with screwdriver Philips No 3
|
Width
|
45 mm
|
Height
|
121 mm
|
Depth
|
115 mm
|
Net weight
|
0.255 kg
|
Environment
Ambient air temperature for storage
|
-25…70 °C
|
Ambient air temperature for operation
|
-10…50 °C without derating
50…60 °C with current derating
|
Relative humidity
|
5…95 %
|
Operating altitude
|
0...2000 m without derating
|
IP degree of protection
|
IP20
|
Pollution degree
|
2
|
Protective treatment
|
TC
|
Fire resistance
|
960 °C conforming to UL 94
850 °C conforming to IEC 60695-2-1
650 °C conforming to IEC 60695-2-12
|
Shock resistance
|
15 gn (duration = 11 ms) conforming to IEC 60068-2-27
|
Vibration resistance
|
1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
|
Electromagnetic compatibility
|
Electrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2
Radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3
Fast transient immunity test, level 4, 4 kV, conforming to EN/IEC 61000-4-4
Surge immunity test (differential mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5
Surge immunity test (common mode), level 4, 4 kV, conforming to EN/IEC 61000-4-5
Conducted RF disturbance immunity test, 20 V, conforming to EN/IEC 61000-4-6
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
5.0 cm
|
Package 1 Width
|
12.5 cm
|
Package 1 Length
|
13.0 cm
|
Package 1 Weight
|
308.0 g
|
Unit Type of Package 2
|
S02
|
Number of Units in Package 2
|
14
|
Package 2 Height
|
15.0 cm
|
Package 2 Width
|
30.0 cm
|
Package 2 Length
|
40.0 cm
|
Package 2 Weight
|
4.657 kg
|
Offer Sustainability
Packaging without single use plastic
|
Yes
|
Packaging made with recycled cardboard
|
Yes
|
SCIP Number
|
0bda50ae-711f-4024-bff6-ce0577049f63
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Compliant with Exemptions
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
Halogen content performance
|
Halogen free plastic parts product
|
Take-back
|
No
|
|
|