Range
|
TeSys
|
Product name
|
TeSys island
|
Device short name
|
TPRST
|
Product or component type
|
Motor starter
|
Motor starter type
|
Direct on line
|
Device presentation
|
Direct starter connected to an automation controller through a bus coupler
Operational only when connected to a bus coupler
|
Function available
|
Upstream voltage presence detection
Electrical line and load protection
Power and energy monitoring when connected with TPRVM voltage module
|
Product compatibility
|
TPRBC bus coupler
TPRVM voltage interface module
|
Poles description
|
3P (3 NO)
|
Utilisation category
|
AC-1
AC-2
AC-3
AC-4
AC-3e
|
Motor power kW
|
2.2 kW at 230 V 50 Hz (AC-3)
4 kW at 380...415 V 50 Hz (AC-3)
4 kW at 440 V 50 Hz (AC-3)
5.5 kW at 500 V 50 Hz (AC-3)
5.5 kW at 690 V 50 Hz (AC-3)
|
Motor power HP (UL / CSA)
|
0.33 hp at 120 V AC 60 Hz for 1 phase motors
1 hp at 240 V AC 60 Hz for 1 phase motors
2 hp at 208 V AC 60 Hz for 3 phases motors
2 hp at 240 V AC 60 Hz for 3 phases motors
5 hp at 480 V AC 60 Hz for 3 phases motors
7.5 hp at 600 V AC 60 Hz for 3 phases motors
|
[Ue] rated operational voltage
|
<= 690 V AC 47...63 Hz
|
[Ie] rated operational current
|
9 A (at <50 °C) at <= 440 V AC-3
15 A (at <50 °C) at <= 440 V AC-1
|
[Ith] conventional free air thermal current
|
15 A (at 50 °C)
|
[Ui] rated insulation voltage
|
690 V conforming to IEC 60947-4-1
600 V conforming to UL 60947-4-1
600 V conforming to CSA C22.2 No 60947-4-1
|
[Uimp] rated impulse withstand voltage
|
6 kV conforming to IEC 60947-1
|
Overvoltage category
|
III
|
Thermal protection adjustment range
|
0.18…9 A
|
Thermal overload class
|
Class 5…30
|
Reset
|
Remotely or automatically
|
Irms rated making capacity
|
250 A at 440 V conforming to IEC 60947
|
Rated breaking capacity
|
250 A at 440 V conforming to IEC 60947
|
[Icw] rated short-time withstand current
|
210 A 40 °C - 1 s
105 A 40 °C - 10 s
61 A 40 °C - 1 min
30 A 40 °C - 10 min
|
Average impedance
|
2.5 mOhm - Ith 15 A 50 Hz
|
Power dissipation per pole
|
0.2 W AC-3 - Ith 9 A
0.56 W AC-1 - Ith 15 A
|
[Uc] control circuit voltage
|
24 V DC supplied by the bus coupler
|
Current consumption
|
160 mA contactor sealed
160 mA contactor closing
|
Power dissipation in W
|
3.5 W at Ie AC-3
|
Mechanical durability
|
30 Mcycles
|
Electrical durability
|
2 Mcycles 9 A AC-3 at Ue 440 V
1.2 Mcycles 15 A AC-1 at Ue 440 V
|
Maximum operating rate
|
3600 cyc/mn AC-3
|
Operating time
|
< 100 ms closing
< 30 ms opening
|
Safety performance level
|
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
|
Protection type
|
Thermal overload protection
Motor overheat
Overcurrent
Undercurrent
Jam
Long start
Stall
Rapid cycle lockout
Phase sequence
Rapid restart lockout
Phase reversal
Phase loss
Phase unbalance
Ground current
|
Monitoring type
|
Time device ON
Time device switch ON
Number of faults
Number of switching cycles
Number of device power cycles
Average current Iavg
Average voltage Vavg
Max current Imax
Max voltage Vmax
Active and reactive power with voltage module
Active and reactive energy with voltage module
True power factor with voltage module
|
Local signalling
|
1 LED (green/red) for DS (device status)
1 LED (green/red) for LS (load status)
|
Standards
|
EN/IEC 60947-1
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
|
Product certifications
|
EAC
CSA
CCC
UL
|
Mounting mode
|
Horizontal and vertical (35 mm symmetrical DIN rail)
|
Connections - terminals
|
Screw-clamp terminals 1 cable(s) 1…4 mm² (AWG 16...AWG 12) rigid
Screw-clamp terminals 2 cable(s) 1…4 mm² (AWG 16...AWG 12) rigid
Screw-clamp terminals 1 cable(s) 1.5…4 mm² (AWG 16...AWG 12) flexible without cable end
Screw-clamp terminals 2 cable(s) 1.5…4 mm² (AWG 16...AWG 12) flexible without cable end
Screw-clamp terminals 1 cable(s) 1…4 mm² (AWG 16...AWG 12) flexible with cable end
Screw-clamp terminals 2 cable(s) 1…2.5 mm² (AWG 16...AWG 14) flexible with cable end
|
Tightening torque
|
1.7 N.m - with screwdriver flat Ø 6 mm
1.7 N.m - with screwdriver Philips No 2
|
Width
|
45 mm
|
Height
|
116 mm
|
Depth
|
115 mm
|
Net weight
|
0.656 kg
|
Ambient air temperature for storage
|
-25…70 °C
|
Ambient air temperature for operation
|
-10…50 °C without derating
50…60 °C with current derating
|
Relative humidity
|
5…95 %
|
Operating altitude
|
0...2000 m without derating
|
IP degree of protection
|
IP20
|
Pollution degree
|
2
|
Protective treatment
|
TC
|
Fire resistance
|
960 °C conforming to UL 94
850 °C conforming to IEC 60695-2-1
650 °C conforming to IEC 60695-2-12
|
Shock resistance
|
15 gn (duration = 11 ms) conforming to IEC 60068-2-27
|
Vibration resistance
|
1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
|
Electromagnetic compatibility
|
Electrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2
Radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3
Fast transient immunity test, level 4, 4 kV, conforming to EN/IEC 61000-4-4
Surge immunity test (differential mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5
Surge immunity test (common mode), level 4, 4 kV, conforming to EN/IEC 61000-4-5
Conducted RF disturbance immunity test, 20 V, conforming to EN/IEC 61000-4-6
|