Mounting Support
|
Door
|
Performance Level
|
High performance
|
Number of Poles
|
3P
|
Contact Type and Composition
|
3 NO
|
Color
|
Grey
|
[Ue] UL Rated Operational Voltage
|
600 V AC 50/60 Hz conforming to UL 508
|
Network type
|
AC
|
Network frequency
|
50/60 Hz
|
UL Maxium Horsepower Ratings
|
5 hp at 200/208 V AC
5 hp at 240 V AC
10 hp at 480 V AC
10 hp at 600 V AC
1 hp at 120 V AC
2 hp at 240 V AC
|
[Ue] IEC Rated Operational Voltage
|
690 V AC 50/60 Hz
|
IEC Rated Operational Power in W
|
7.5 kW at 400 V (AC-23A)
7.5 kW at 500 V (AC-23A)
11 kW at 690 V (AC-23A)
|
[Ie] Rated Operational Current
|
16 A Ue: 600 V conforming to UL 508
16 A AC-21A Ue: 400 V
16 A AC-21A Ue: 500 V
16 A AC-21A Ue: 690 V
16 A AC-22A Ue: 400 V
16 A AC-22A Ue: 500 V
16 A AC-22A Ue: 690 V
16 A AC-23A Ue: 400 V
16 A AC-23A Ue: 500 V
16 A AC-23A Ue: 690 V
|
[Ith] Conventional Free Air Thermal Current
|
16 A (at 55 °C)
|
[Ithe] Conventional Enclosed Thermal Current
|
16 A
|
Making capacity ( I Rms)
|
24 A at 690 V AC-21A
48 A at 690 V AC-22A
160 A at 690 V AC-23A
|
Breaking Capacity
|
24 A at 690 V (AC-21A)
48 A at 690 V (AC-22A)
128 A at 690 V (AC-23A)
|
SCCR
|
Fuse RK5 30 A maximum: 5 kA at 600 V AC
|
Rated Conditional Short Circuit Current
|
50 kA at 400 V - associated fuse 16 A gG
|
[Icm] Rated Short Circuit Making Capacity
|
1128 A at 690 V
|
Intermittent duty class
|
Class 120 - 60 %
|
[Uimp] rated impulse withstand voltage
|
8 kV
|
[Icw] rated short-time withstand Rms current
|
800 A at 690 V duration: 1 s
|
Mechanical Durability
|
100000 cycles
|
Electrical Durability
|
100000 cycles AC-21A
|
UL Wire Size
|
AWG 18...AWG 6 copper
|
IEC Terminal Connection
|
Power circuit: screw clamp terminals10 mm² - solid
Power circuit: screw clamp terminals16 mm² - flexible - without cable end
|
Tightening Torque
|
Power circuit: 1.8…2 N.m - on screw clamp terminals
|
Height
|
78 mm
|
Width
|
45 mm
|
Depth
|
73 mm
|
Product Weight
|
0.135 kg
|