XPSBAC14AP
safety module, Harmony XPS, estop or guard, connected to supply terminals 24V AC or DC , no inputs, screw
|
|
|
Main
Range of product
|
Harmony Safety Automation
|
Product or component type
|
Safety module
|
Safety module name
|
XPSBAC
|
Safety module application
|
For emergency stop and protective guard applications
|
Function of module
|
Emergency stop button with 2 NC contacts
Guard monitoring with 1 or 2 limit switches
|
Safety level
|
Can reach PL e/category 4 for normally open relay contact conforming to ISO 13849-1
Can reach SILCL 3 for normally open relay contact conforming to IEC 62061
Can reach SIL 3 for normally open relay contact conforming to IEC 61508
Can reach PL c/category 1 for normally closed relay contact conforming to ISO 13849-1
Can reach SILCL 1 for normally closed relay contact conforming to IEC 62061
Can reach SIL 1 for normally closed relay contact conforming to IEC 61508
|
Safety reliability data
|
MTTFd > 30 years conforming to ISO 13849-1 for normally open relay contact
Dcavg >= 99 % conforming to ISO 13849-1 for normally open relay contact
PFHd = 0.95E-09 conforming to ISO 13849-1 for normally open relay contact
HFT = 1 conforming to IEC 62061 for normally open relay contact
PFHd = 0.95E-09 conforming to IEC 62061 for normally open relay contact
SFF > 99% conforming to IEC 62061 for normally open relay contact
HFT = 1 conforming to IEC 61508-1 for normally open relay contact
PFHd = 0.95E-09 conforming to IEC 61508-1 for normally open relay contact
SFF > 99% conforming to IEC 61508-1 for normally open relay contact
Type = B conforming to IEC 61508-1 for normally open relay contact
MTTFd > 30 years conforming to ISO 13849-1 for normally closed relay contact
DC > 60 % conforming to ISO 13849-1 for normally closed relay contact
PFHd = 0.95E-09 conforming to ISO 13849-1 for normally closed relay contact
HFT=0 conforming to IEC 62061 for normally closed relay contact
PFHd = 0.95E-09 conforming to IEC 62061 for normally closed relay contact
SFF > 60% conforming to IEC 62061 for normally closed relay contact
HFT=0 conforming to IEC 61508-1 for normally closed relay contact
PFHd = 0.95E-09 conforming to IEC 61508-1 for normally closed relay contact
SFF > 60% conforming to IEC 61508-1 for normally closed relay contact
Type = B conforming to IEC 61508-1 for normally closed relay contact
|
Electrical circuit type
|
NC pair
|
Connections - terminals
|
Removable screw terminal block, 0.2...2.5 mm² solid or flexible
Removable screw terminal block, 0.25...2.5 mm² flexible with ferrule single conductor
Removable screw terminal block, 0.2...1.5 mm² solid or flexible twin conductor
Removable screw terminal block, 2 x 0.25...1 mm² flexible with ferrule without cable end, with bezel
Removable screw terminal block, 2 x 0.5...1.5 mm² flexible with ferrule with cable end, with bezel
|
[Us] rated supply voltage
|
24 V AC - 15...10 %
24 V DC - 20...20 %
|
Complementary
Synchronisation time between inputs
|
Unlimited
|
Type of start
|
Automatic/manual/monitored
|
Power consumption in W
|
1.5 W 24 V DC
|
Power consumption in VA
|
3.5 VA 24 V AC 50/60 Hz
|
Input protection type
|
Internal, electronic
|
Safety outputs
|
4 NO + 1 NC
|
Safety inputs
|
0
|
Input compatibility
|
Normally closed circuit conforming to ISO 14119
XC limit switch conforming to ISO 14119
Mechanical contact conforming to ISO 14119
Normally closed circuit conforming to ISO 13850
|
Input terminal
|
Power supply
|
[Ie] rated operational current
|
5 A AC-1 for normally open relay contact
3 A AC-15 for normally open relay contact
5 A DC-1 for normally open relay contact
3 A DC-13 for normally open relay contact
3 A AC-1 for normally closed relay contact
1 A AC-15 for normally closed relay contact
3 A DC-1 for normally closed relay contact
1 A DC-13 for normally closed relay contact
|
Control outputs
|
0
|
[Ith] conventional free air thermal current
|
6 A
|
Associated fuse rating
|
10 A gG for NO relay output circuit conforming to IEC 60947-1
|
Minimum output current
|
10 mA for relay output
|
Minimum output voltage
|
5 V for relay output
|
Response time
|
150 ms at 24 V AC
80 ms at 24 V DC
|
[Ui] rated insulation voltage
|
300 V (pollution degree 2) conforming to IEC 60947-1
|
[Uimp] rated impulse withstand voltage
|
4 kV overvoltage category II conforming to IEC 60947-1
|
Local signalling
|
LED green with power marking for power ON
LED red with error marking for error
LED yellow with state marking for status
LED yellow with start1 marking for start input
LED yellow with start2 marking for start input
|
Mounting support
|
35 mm symmetrical DIN rail
|
Depth
|
120 mm
|
Height
|
100 mm
|
Width
|
22.5 mm
|
Net weight
|
0.200 kg
|
Environment
Ambient air temperature for operation
|
-25…55 °C
|
Standards
|
IEC 60947-5-1
IEC 61508-1 functional safety standard
IEC 61508-2 functional safety standard
IEC 61508-3 functional safety standard
IEC 61508-4 functional safety standard
IEC 61508-5 functional safety standard
IEC 61508-6 functional safety standard
IEC 61508-7 functional safety standard
ISO 13849-1 functional safety standard
IEC 62061 functional safety standard
|
Product certifications
|
TÜV
cULus
|
IP degree of protection
|
IP20 (terminals) conforming to IEC 60529
IP40 (housing) conforming to IEC 60529
IP54 (mounting area) conforming to IEC 60529
|
Relative humidity
|
5…95 % non-condensing
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
6.500 cm
|
Package 1 Width
|
13.500 cm
|
Package 1 Length
|
15.500 cm
|
Package 1 Weight
|
301.000 g
|
Unit Type of Package 2
|
S03
|
Number of Units in Package 2
|
16
|
Package 2 Height
|
30.000 cm
|
Package 2 Width
|
30.000 cm
|
Package 2 Length
|
40.000 cm
|
Package 2 Weight
|
5.556 kg
|
Unit Type of Package 3
|
P06
|
Number of Units in Package 3
|
128
|
Package 3 Height
|
75.000 cm
|
Package 3 Width
|
60.000 cm
|
Package 3 Length
|
80.000 cm
|
Package 3 Weight
|
52.000 kg
|
Offer Sustainability
SCIP Number
|
152cf799-1df7-4892-81b4-4c890187f1d1
|
Packaging without single use plastic
|
No
|
Packaging made with recycled cardboard
|
No
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
|
Mercury free
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
RoHS exemption information
|
Yes
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg CO2 eq, Total Life cycle)
|
55
|
|
|