Max power consumption in W
|
60 mW
|
Number of channels
|
16
|
Modulation Technique
|
O-QPSK
|
Bandwidth
|
5 MHz
|
Antenna gain
|
0 dBi
|
CAD overall height
|
21 mm
|
CAD overall width
|
40 mm
|
CAD overall depth
|
40 mm
|
Net weight
|
0.034 kg
|
Measurement temperature
|
90 °C
|
Mechanical robustness
|
Free fall resistance 1000 mm conforming to IEC 60068-2-32
|
Standards
|
IEC 61010-1
UL 61010-1
IEEE 802.15.4
|
Radio agreement
|
ANATEL
ARIB T66
FCC
ICASA
RSS
SRRC
|
Communication port protocol
|
Zigbee green power at 2.4 GHz conforming to IEEE 802.15.4
|
Maximum sensing distance
|
100 m in free field
25 m transmitter in a plastic box type XAL D and receiver in a metal enclosure
10 m transmitter in box type XAL D, receiver in metal enclosure and use relay-antenna
|
Acquisition time
|
2 ms
|
Response time
|
< 2 ms
|
Fixing mode
|
Magnetic fixing
|
Mounting mode
|
Magnetic
|
Electrical composition code
|
PW1
|
Ambient air temperature for storage
|
-40…70 °C
|
Ambient air temperature for operation
|
-40…70 °C
|
Relative humidity
|
10…95 % at -40…70 °C
|
IP degree of protection
|
IP54 conforming to IEC 60529
|
IK degree of protection
|
IK06 conforming to IEC 62262
|
Shock resistance
|
40 gn (duration = 6 ms) for 3 shocks conforming to IEC 60068-2-27
20 gn (duration = 16 ms) for 1000 shocks conforming to IEC 60068-2-27
10 gn (duration = 11 ms) for 3 shocks conforming to IEC 60068-2-27
|
Vibration resistance
|
2 gn (f= 5…200 Hz) conforming to IEC 60068-2-6
4 gn (f= 200…500 Hz) conforming to IEC 60068-2-6
1 gn (f= 10…2000 Hz) conforming to IEC 60068-2-64
1 gn (f= 5…500 Hz) conforming to IEC 60068-2-6
|
Electromagnetic compatibility
|
Susceptibility to electromagnetic fields - test level: 25 V/m (80 MHz...6 GHz) conforming to IEC 61000-4-3
Susceptibility to conducted disturbances - test level: 20 V (0.15...80 MHz) conforming to IEC 61000-4-6
Electromagnetic field immunity test - test level: 1000 A/m (pulsed) conforming to IEC 61000-4-8
Electromagnetic field immunity test - test level: 300 A/m (continuous) conforming to IEC 61000-4-8
Electromagnetic field immunity test - test level: 1000 A/m (pulsed) conforming to EN/IEC 61000-4-9
Damped oscillatory wave - test level: 3 kV conforming to IEC 61000-4-10
Damped oscillatory wave - test level: 2.5 kV conforming to EN/IEC 61000-4-18
Surge immunity test conforming to EN/IEC 61000-4-18
Surge immunity test (common mode) conforming to IEC 61000-4-5
Immunity to conducted RF disturbances - test level: 30 V (differential mode) conforming to IEC 61000-4-5
Immunity to conducted RF disturbances (continuous) conforming to IEC 61000-4-16
Immunity to conducted RF disturbances - test level: 300 V
Immunity to conducted RF disturbances (short term) conforming to IEC 61000-4-16
|
Product certifications
|
CSA
CCC
UL
GOST
C-Tick
BT 2006/95/EC
|
Directives
|
2004/108/EC - electromagnetic compatibility
1999/5/EC - R&TTE directive
|