Analogue input number
|
16
|
Input type
|
Differential
|
Addressing requirement
|
17 input words
|
Analogue input resolution
|
0...16000 counts 4...20 mA
0...20000 counts 0...20 mA
0...25000 counts 0...25 mA
0...4095 counts 4...20 mA
|
Absolute maximum input
|
30 mA
|
Input impedance
|
250 Ohm
|
Absolute accuracy error
|
+/- 0.125 % of full scale
|
Linearity error
|
+/- 12 µA max 4...20 mA
+/- 6 µA max 0...20 mA
+/- 6 µA max 0...25 mA
+/- 6 µA max 4...20 mA
|
Accuracy drift according to temperature
|
+/- 0.0025 % of full scale/°C
<= 0.0050 % of full scale /°C
|
Common mode rejection
|
> - 90 dB 60 Hz
|
Isolation between channels and bus
|
1780 V AC for 60 s
|
Update time
|
15 ms 2 wires/4 wires
|
Fault type
|
Broken wire 4...20 mA
|
Marking
|
CE
|
Local signalling
|
1 LED (green) for bus communication is present (Active)
1 LED (red) for external fault
16 LEDs (green) for channel is turned on
16 LEDs (red) for channel fault
|
Bus current requirement
|
360 mA
|
Power dissipation in W
|
5 W
|
Module format
|
Standard
|
Net weight
|
0.3 kg
|