Group of channels
|
4 groups of 8
|
Discrete output logic
|
Negative logic (sink)
|
Addressing requirement
|
2 output words
|
Discrete output voltage
|
24 V DC
|
Output voltage limits
|
19.2...30 V
|
Absolute maximum output
|
50 V for 1 s decaying pulse
|
Maximum voltage drop
|
<0.4 V 0.5 A
|
Maximum load current
|
16 A per module
4 A per group
|
Surge current
|
5 A for 1 ms
|
Response time
|
<= 1 ms at state 0 to state 1
<= 1 ms at state 1 to state 0
|
Maximum leakage current
|
0.4 mA 30 V
|
Load inductance
|
Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz)))
|
Maximum tungsten load
|
12 W 24 V
|
Fault indication
|
Loss of field power
Blown fuse
|
Associated fuse rating
|
3 A each point
5 A per group
|
Isolation between channels and bus
|
1780 Vrms DC for 1 minute
|
Isolation between group
|
500 Vrms DC for 1 minute
|
Protection type
|
Internal output protection by 5 A fuse per group
|
Power dissipation
|
2.0 W + (0.4 V x total load current)
|
Marking
|
CE
|
Local signalling
|
1 LED (green) for bus communication is present (Active)
1 LED (red) for external fault detected (F)
32 LEDs (green) for input status
|
Bus current requirement
|
330 mA
|
Module format
|
Standard
|
Net weight
|