Contacts type and composition
|
1 NO/NC
|
Contact form
|
Form C
|
Discrete output voltage
|
20...250 V AC
30...150 V DC
5...30 V DC
|
Addressing requirement
|
0.5 output word
|
Maximum load current
|
100 mA 30...50 V DC L/R = 10 ms
2 A 250/30 V AC/DC tungsten 1/4 hp cos phi = 0.4
3 A 250/30 V AC/DC
300 mA 30...50 V DC resistive
5 A 250/30 V AC/DC resistive at 60 °C
|
Surge current
|
20 A for 10 ms capacitive
|
Switching frequency
|
30 Hz resistive load
F = 0.5/I²L inductive load
|
Switching capacity in VA
|
1250 VA resistive
|
Maximum response time on input open
|
10 ms at state 0 to state 1
20 ms at state 1 to state 0
|
Mechanical durability
|
10000000 cycles
|
Electrical durability
|
100000 cycles 100 mA 30...150 V DC L/R = 10 ms
100000 cycles 30...150 V DC interposing relay
100000 cycles 300 mA 30...150 V DC resistive
100000 cycles 5 A 30 V DC resistive
200000 cycles 5 A 250 V AC resistive
50000 cycles 500 mA 30...150 V DC resistive
|
Output overvoltage protection
|
Internal by varistor, 275 V
|
Isolation between channels
|
1780 Vrms AC for 1 minute
2500 V DC
|
Isolation between channels and bus
|
1780 Vrms AC for 1 minute
2500 V DC for 1 minute
|
Power dissipation
|
2.75 W + (0.5 x the number of points on)
|
Marking
|
CE
|
Local signalling
|
1 LED (green) for bus communication is present (Active)
1 LED (red) for external fault detected (F)
8 LEDs (green) for input status
|
Bus current requirement
|
560 mA
|
Module format
|
Standard
|
Net weight
|
0.3 kg
|