Data format
|
Full 16 bits signed
|
Absolute accuracy error
|
+/- 0.13 % full scale 25 °C 1...5 V
+/- 0.19 % full scale 60 °C 1...5 V
+/- 0.21 % full scale 25 °C +/- 5 V
+/- 0.26 % full scale 60 °C +/- 5 V
+/- 0.27 % full scale 25 °C +/- 10 V
+/- 0.27 % full scale 25 °C 4...20 mA
+/- 0.32 % full scale 25 °C +/- 20 mA
+/- 0.32 % full scale 60 °C +/- 10 V
+/- 0.38 % full scale 60 °C 4...20 mA
+/- 0.41 % full scale 60 °C +/- 20 mA
|
Conversion time
|
12 ms 8
|
Isolation between channels
|
+/- 200 V DC for 1 minute
|
Isolation between channels and ground
|
500 V AC for 1 minute
|
Isolation between channels and bus
|
500 V AC for 1 minute
|
Permissible common mode voltage
|
100 V 47...63 Hz DC between channels to ground
250 V 47...63 Hz AC between channels to ground
|
Common mode rejection
|
> 80 dB between channels to ground
|
External power requirement
|
< 382 mA DC
20.4...28.8 V DC
24 V DC
|
Reverse polarity protection
|
Internal
|
Marking
|
CE
|
Local signalling
|
1 LED (green) for ready
8 LEDs for channel status
|
Electrical connection
|
2 connectors for removable terminal blocks
|
Depth
|
47.5 mm
|
Height
|
125 mm
|
Width
|
141.5 mm
|
Net weight
|
0.215 kg
|