[Us] rated supply voltage
|
24 V DC
|
Input voltage limits
|
- 3...30 V
|
Network frequency
|
47...63 Hz
|
Voltage state 0 guaranteed
|
-3...5 V
|
Voltage state 1 guaranteed
|
11...30 V
|
Current state 0 guaranteed
|
<= 1.2 mA
|
Current state 1 guaranteed
|
>= 2.5 mA
|
Input resistance
|
4 kOhm
|
Discrete output current
|
<= 0.15 mA 115 V inductive
<= 0.5 mA 115 V resistive
<= 1 mA 24 V inductive
<= 2 mA 24 V resistive
>= 0.005 A 24 V
|
Maximum leakage current
|
1 mA at 230 V (output circuit)
|
Mechanical durability
|
30000000 cycles
|
Electrical durability
|
100000 cycles inductive
|
Response time
|
10 ms 60 Hz from state 0 to state 1 on output
10 ms 60 Hz from state 1 to state 0 on output
2.2 ms from state 0 to state 1 on input
3.3 ms from state 1 to state 0 on input
|
Isolation between channels and bus
|
500 V AC
|
Power dissipation
|
5.5 W
<= 8.5 W
|
Protection type
|
Without protection
|
Associated fuse rating
|
4 A fast blow input voltage
8 A slow-blow output voltage per group
375 mA fast blow operating voltage
|
Marking
|
CE
|
Terminals description PLC n°1
|
(1L+)PW_POS
(3)IN_DIS#3
(9)IN_DIS#9
(1)IN_DIS#1
(8)IN_DIS#8
(6)IN_DIS#6
(2)IN_DIS#2
(7)IN_DIS#7
(4)IN_DIS#4
(L+)PW_POS
(10)IN_DIS#10
(5)IN_DIS#5
(M-)PW_NEG
TB
|
Terminals description PLC n°2
|
(6)OUT_DIS#6
(2L1)PW
(2)OUT_DIS#2
TB_1
(8)OUT_DIS#8
(7)OUT_DIS#7
(1L+)PW
(4)OUT_DIS#4
(5)OUT_DIS#5
(1)OUT_DIS#1
(3)OUT_DIS#3
|
Current consumption
|
250 mA at 24 V DC
|
Depth
|
47.5 mm
|
Height
|
141.5 mm
|
Width
|
125 mm
|
Net weight
|
0.26 kg
|