Concept
|
Transparent Ready class B
|
Web services
|
Bandwidth monitoring
Properties
CPU status
Ethernet statistics
Home pages
|
Software designation
|
Unity Pro
|
Communication service
|
Modbus messaging 125 words, 200 I/O message per second
Global Data, 2200 I/O message per second
Modbus TCP I/O Scanner and Messaging
|
Processor name
|
Spear 320s
|
Word length
|
32 bit
|
Supply voltage limits
|
4.75…5.25 V
|
Clock frequency
|
333 MHz
|
Topology
|
Multidrop Modbus
Star Modbus TCP
|
Communication port protocol
|
Modbus RS485/RS232 - 1 RJ45 19200 bps - 2-wire
Modbus TCP ETHERNET - 1 RJ45 10/100 Mbps - twisted shielded pairs cable CAT 5E UTP
|
Method of access
|
Client/server
Master/slave
|
Control parameter
|
CRC-32 for Modbus TCP/IP
CRC-16 for Modbus
|
Addressing
|
1...247 Modbus
Unique IEEE global address Modbus TCP
|
Fail state
|
Safe I/O mode
|
Memory description
|
Program memory IEC 3584 kB
Program memory LL984 3584 kB
|
Register words
|
26048
|
I/O limit processor capacity
|
2048 inputs/2048 outputs
|
Number of devices
|
32 Modbus
|
Exact time for 1 Kinstruction
|
83 ns
|
Local signalling
|
1 LED (green) for processor running (RUN)
1 LED (red) for processor or system fault (ERR)
1 LED (red) for I/O module fault (I/O)
1 LED (yellow) for channel 0 operating (CH0)
1 LED (green) for data rate (ETH 100)
1 LED (green) for data rate (ETH LINK)
1 LED (green) for status of Ethernet network (ETH STS)
|
Marking
|
CE
|
Current consumption
|
500 mA at 5 V DC
|
Module format
|
Standard
|
Product mounting
|
35 mm symmetrical DIN rail
|
Height
|
60.6 mm
|
Width
|
144 mm
|
Depth
|
53.47 mm
|
Net weight
|
0.163 kg
|
Material
|
Lexan
|
Dielectric strength
|
0 V not isolated RS485/RS232
5000 V for 1 minute ETHERNET
|
Product certifications
|
C-Tick
FM
|
Standards
|
UL 508
CSA C22.2 No 142
EN/IEC 61131-2
|
IP degree of protection
|
IP20
|
Shock resistance
|
15 gn during 11 ms sinusoidal vibrations
|
Resistance to electrostatic discharge
|
6 kV contact conforming to EN/IEC 61131-2 zone B
6 kV contact conforming to IACS E10
8 kV on air conforming to EN/IEC 61000-4-2
|
Resistance to electromagnetic fields
|
15 V/m 80...2700 MHz conforming to EN/IEC 61000-4-3
|
Ambient air temperature for operation
|
0…60 °C
|
Ambient air temperature for storage
|
-40…85 °C
|
Relative humidity
|
5…96 %
|
Operating altitude
|
<= 2000 m
|