Network frequency
|
50/60 Hz
|
[Ue] rated operational voltage
|
380...415 V AC 50/60 Hz
125 V DC
<= 144 V DC
12 V DC
220...240 V AC 50/60 Hz
110...130 V AC 50/60 Hz
|
Magnetic tripping limit
|
8 x In
|
[Ics] rated service breaking capacity
|
37.5 kA 75 % conforming to EN/IEC 60947-2 - 110...130 V AC 50/60 Hz
18.75 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
4.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz
25 kA 100 % conforming to EN/IEC 60947-2 - 60 V DC
25 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC
|
[Ui] rated insulation voltage
|
690 V AC 50/60 Hz conforming to EN/IEC 60947-2
|
[Uimp] rated impulse withstand voltage
|
8 kV conforming to EN/IEC 60947-2
|
Contact position indicator
|
Yes
|
Control type
|
Manual tripping test
Toggle
|
Local signalling
|
Trip indicator
ON/OFF indication
|
Mounting mode
|
Clip-on
|
Mounting position
|
Vertical
|
Mounting support
|
35 mm symmetrical DIN rail
|
Comb busbar and distribution block compatibility
|
YES
|
9 mm pitches
|
3
|
Height
|
103 mm
|
Depth
|
81 mm
|
Width
|
27 mm
|
Net weight
|
0.24 kg
|
Mechanical durability
|
20000 cycles
|
Electrical durability
|
10000 cycles
|
Provision for padlocking
|
Padlockable
|
Locking options description
|
Integrated padlocking
|
Connections - terminals
|
Tunnel type terminals1.5…50 mm² rigid
Tunnel type terminals1…35 mm² flexible
|
Wire stripping length
|
20 mm
|
Tightening torque
|
3.5 N.m
|
Earth-leakage protection
|
Without
|