Network frequency
|
50/60 Hz
|
[Ue] rated operational voltage
|
440 V AC 50/60 Hz
230...240 V AC 50/60 Hz
400...415 V AC 50/60 Hz
500 V AC 50/60 Hz
690 V AC 50/60 Hz
|
Magnetic tripping limit
|
12 x In
|
[Ics] rated service breaking capacity
|
2.25 kA conforming to EN/IEC 60947-2 - 690 V AC 50/60 Hz
4 kA conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
4.5 kA conforming to EN/IEC 60947-2 - 500 V AC 50/60 Hz
7.5 kA conforming to EN/IEC 60947-2 - 400...415 V AC 50/60 Hz
|
[Ui] rated insulation voltage
|
690 V AC 50/60 Hz conforming to EN/IEC 60947-2
|
Contact position indicator
|
Yes
|
Control type
|
Manual tripping test
Toggle
|
Local signalling
|
ON/OFF indication
|
Mounting mode
|
Clip-on
|
Mounting support
|
35 mm symmetrical DIN rail
|
9 mm pitches
|
5
|
Height
|
89 mm
|
Width
|
45 mm
|
Depth
|
70 mm
|
Net weight
|
0.26 kg
|
Electrical durability
|
AC-3: 100000 cycles AC 50/60 Hz conforming to IEC 60947-2
|
Provision for padlocking
|
Padlockable
|
Locking options description
|
Integrated padlocking
|
Connections - terminals
|
Clamps terminal2 cable(s) 1…6 mm² rigid
Clamps terminal2 cable(s) 1…6 mm² flexible
|
Tightening torque
|
1.7 N.m
|
Earth-leakage protection
|
Without
|