31106
switch disconnector, Compact INS250, 250A, standard version with black rotary handle, 3 poles
|
|
|
Main
Range
|
ComPact
|
Product or component type
|
Switch disconnector
|
Product name
|
ComPacT INS
|
Poles description
|
3P
|
Network type
|
DC
AC
|
Network frequency
|
50/60 Hz
|
[Ie] rated operational current
|
AC-22A: 250 A AC 50/60 Hz 220/240 V
AC-22A: 250 A AC 50/60 Hz 380/415 V
AC-22A: 250 A AC 50/60 Hz 440/480 V
AC-22A: 250 A AC 50/60 Hz 480 V NEMA
AC-22A: 250 A AC 50/60 Hz 500/525 V
AC-22A: 250 A AC 50/60 Hz 660/690 V
AC-23A: 250 A AC 50/60 Hz 220/240 V
AC-23A: 250 A AC 50/60 Hz 380/415 V
AC-23A: 250 A AC 50/60 Hz 440/480 V
AC-23A: 250 A AC 50/60 Hz 480 V NEMA
AC-23A: 250 A AC 50/60 Hz 500/525 V
AC-23A: 250 A AC 50/60 Hz 660/690 V
DC-22A: 250 A DC 125 V 2 poles in series
DC-23A: 250 A DC 125 V 2 poles in series
|
[Ui] rated insulation voltage
|
800 V AC 50/60 Hz
|
[Ith] conventional free air thermal current
|
250 A at 60 °C
|
[Icm] rated short-circuit making capacity
|
30 kA switch-disconnector alone 690 V AC at 50/60 Hz
330 kA with upstream protection circuit breaker 690 V AC at 50/60 Hz
|
[Ue] rated operational voltage
|
125 V DC
690 V AC 50/60 Hz
|
Suitability for isolation
|
Yes
|
Contact position indicator
|
Yes
|
Visible break
|
No
|
Pollution degree
|
3
|
Complementary
Control type
|
Direct front rotary handle
|
Handle colour
|
Black
|
Mounting mode
|
Fixed
|
Mounting support
|
Rail
Plate
|
Upside connection
|
Front
|
Downside connection
|
Front
|
Maximum power
|
AC-23: 132 kW at 380/415 V AC 50/60 Hz
AC-23: 150 kW at 440 V AC 50/60 Hz
AC-23: 150 kW at 480 V AC 50/60 Hz (NEMA)
AC-23: 160 kW at 500/525 V AC 50/60 Hz
AC-23: 210 kW at 660/690 V AC 50/60 Hz
AC-23: 75 kW at 220/240 V AC 50/60 Hz
AC-23: 75 kW at 230 V AC 50/60 Hz (NEMA)
|
Rated duty
|
Uninterrupted
|
[Icw] rated short-time withstand current
|
1.8 kA during 30 s conforming to IEC 60947-3
2.2 kA during 20 s conforming to IEC 60947-3
4.9 kA during 3 s conforming to IEC 60947-3
8.5 kA during 1 s conforming to IEC 60947-3
|
Mechanical durability
|
15000 cycles
|
Electrical durability
|
AC-22A: 1500 cycles 440 V AC 50/60 Hz
AC-22A: 1500 cycles 500 V AC 50/60 Hz
AC-22A: 1500 cycles 690 V AC 50/60 Hz
AC-23A: 1500 cycles 440 V AC 50/60 Hz
AC-23A: 1500 cycles 500 V AC 50/60 Hz
AC-23A: 1500 cycles 690 V AC 50/60 Hz
DC-22A: 1500 cycles 125 V DC 2 poles in series
DC-23A: 1500 cycles 125 V DC 2 poles in series
|
Connection pitch
|
35 mm
|
Height
|
136 mm
|
Width
|
140 mm
|
Depth
|
96 mm
|
Net weight
|
2 kg
|
Environment
Standards
|
IEC 60947-3
IEC 60947-1
|
Product certifications
|
KEMA-KEUR
CCC
|
IP degree of protection
|
IP40 conforming to IEC 60529
|
IK degree of protection
|
IK07 conforming to EN 50102
|
Ambient air temperature for operation
|
-25…70 °C
|
Ambient air temperature for storage
|
-50…85 °C
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
13.800 cm
|
Package 1 Width
|
16.200 cm
|
Package 1 Length
|
17.400 cm
|
Package 1 Weight
|
2.216 kg
|
Unit Type of Package 2
|
S04
|
Number of Units in Package 2
|
9
|
Package 2 Height
|
30.000 cm
|
Package 2 Width
|
40.000 cm
|
Package 2 Length
|
60.000 cm
|
Package 2 Weight
|
20.710 kg
|
Unit Type of Package 3
|
P12
|
Number of Units in Package 3
|
36
|
Package 3 Height
|
50.000 cm
|
Package 3 Width
|
80.000 cm
|
Package 3 Length
|
120.000 cm
|
Package 3 Weight
|
92.712 kg
|
Offer Sustainability
Packaging made with recycled cardboard
|
Yes
|
SCIP Number
|
Bbc62998-8aa6-42dc-8088-17a5c936153d
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Compliant with Exemptions
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle)
|
344
|
Contractual warranty
|
|