Schneider-Electric
 
50439 picture- web-product-data-sheet
50439
Closed toroid A type, VigiPacT, Vigilohm, IA80, inner diameter 80mm, rated current 160A
Schneider Electric
Characteristics
Main
Range VigiPacT
Device short name IA80
Product or component type Earth leakage current sensor
Device application Equipment monitoring and control
Range compatibility VigiPacT RH10M residual current protection relay
VigiPacT RH10P residual current protection relay
VigiPacT RH21M residual current protection relay
VigiPacT RH21P residual current protection relay
VigiPacT RH68M residual current protection relay
VigiPacT RH86M residual current protection relay
VigiPacT RH86P residual current protection relay
VigiPacT RH99M residual current protection relay
VigiPacT RH99P residual current protection relay
VigiPacT RH197M residual current protection relay
VigiPacT RH197P residual current protection relay
VigiPacT RHU residual current protection relay
VigiPacT RHUs residual current protection relay
VigiPacT RMH residual current protection relay
Current sensor type A type closed toroid
[Ie] rated operational current 160 A
Complementary
Transformer ratio 1/1000
Network type AC/DC
Network frequency 45...440 Hz
[Icw] rated short-time withstand current 85 kA for 0.5 s
Residual short-circuit withstand current 85 kA / 0.5 s conforming to IEC 60947-2
[Ui] rated insulation voltage 1000 V
Overvoltage category IV
[Uimp] rated impulse withstand voltage 12 kV
Mounting mode Fixed (cables)
Fixed (plain backplate)
Fixed (profiled sheet metal)
Fixed (slotted backplate)
Clip-on (DIN rail)
Calorific value 3.19 MJ
Connections - terminals Screw connection 0.22 mm²
Diameter 80 mm inner:
Cable outer diameter 40 mm: 95 mm² (maximum)
Product weight 0.42 kg
Height 122 mm
Width 150 mm
Depth 44 mm
Environment
IP degree of protection Connectors: IP20
IP30
Environmental characteristic Exposure to damp heat not in service (25...55 °C, RH 95 %) : 28 cycles conforming to IEC 60068-2-30
Salt mist: Kb/2 conforming to IEC 60068-2-52
Exposure to damp heat in service: category C2: 48 hours conforming to IEC 60068-2-56
Pollution degree Level 3 conforming to IEC 60664-1
Ambient air temperature for operation -35…70 °C
Ambient air temperature for storage -55…85 °C
Standards IEC 60947-2
Product certifications CE
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 5.4 cm
Package 1 Width 13.2 cm
Package 1 Length 16.4 cm
Package 1 Weight 332.0 g
Unit Type of Package 2 S04
Number of Units in Package 2 40
Package 2 Height 30.0 cm
Package 2 Width 40.0 cm
Package 2 Length 60.0 cm
Package 2 Weight 14.046 kg
Offer Sustainability
SCIP Number 78b0d24c-0e62-4f91-9397-1958e4735328
REACh Regulation
print REACh Declaration
REACh free of SVHC Yes
EU RoHS Directive Compliant
print EU RoHS Declaration
Toxic heavy metal free Yes
Mercury free Yes
RoHS exemption information
print Yes
China RoHS Regulation
print China RoHS declaration
Environmental Disclosure
print Product Environmental Profile
Circularity Profile
print End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
California proposition 65 WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Take-back No
Carbon footprint (kg CO2 eq, Total Life cycle) 28
Contractual warranty
Warranty 18 months