Number of step output contacts
|
6
|
[Us] rated supply voltage
|
320...460 V AC 50/60 Hz
|
Measurement current
|
0…5 A
|
Operating mode
|
Manual
|
Display type
|
4-digit
7 segments LED
|
Type of measurement
|
Power factor
|
Alarm function
|
5 last alarms
|
Input type
|
Phase to phase
Current input CT...10000/5 A
|
Output type
|
Free outputs contacts current: 1 A 400 V AC 50/60 Hz
Free outputs contacts current: 2 A 250 V AC 50/60 Hz
Free outputs contacts current: 5 A 120 V AC 50/60 Hz
Free outputs contacts current: 0.3 A 110 V DC
Free outputs contacts current: 0.6 A 60 V DC
Free outputs contacts current: 2 A 24 V DC
|
Type of setting
|
Target cos phi: 0.85 inductive...1
|
Measurement accuracy
|
+/- 2 %
|
Time delay range
|
10...1800 s
10...1800 s (on reconnection)
|
Step sequences
|
1.2.2.2
1.2.4.4
1.2.3.6
1.1.2.4
1.2.3.4
1.1.1.1
Linear
1.2.3.3
1.1.2.2
1.1.2.3
1.2.4.8
|
Mounting location
|
Panel
In cabinet
|
Height
|
143 mm
|
Width
|
143 mm
|
Depth
|
67 mm
|
Net weight
|
0.8 kg
|