This Application will be decommissioned as of January 7th 2025

56054 |
Schneider-Electric
 
56054 picture- web-product-data-sheet
56054
Rectangular sensor L2 type, VigiPacT, 470mmx160mm, 3200A
Schneider Electric
Characteristics
Main
Range VigiPacT
Device short name L
Product or component type Earth leakage current sensor
Device application Equipment monitoring and control
Range compatibility VigiPacT RH10M residual current protection relay
VigiPacT RH10P residual current protection relay
VigiPacT RH21M residual current protection relay
VigiPacT RH21P residual current protection relay
VigiPacT RH68M residual current protection relay
VigiPacT RH86M residual current protection relay
VigiPacT RH86P residual current protection relay
VigiPacT RH99M residual current protection relay
VigiPacT RH99P residual current protection relay
VigiPacT RH197M residual current protection relay
VigiPacT RH197P residual current protection relay
VigiPacT RHU residual current protection relay
VigiPacT RHUs residual current protection relay
VigiPacT RMH residual current protection relay
Current sensor type Rectangular sensor
[Ie] rated operational current 3200 A
Complementary
Transformer ratio 1/1000
[Icw] rated short-time withstand current 100 kA for 0.5 s
Residual short-circuit withstand current 85 kA / 0.5 s
Overvoltage category IV
[Uimp] rated impulse withstand voltage 12 kV
Mounting mode Fixed (cables)
Fixed (busbar)
Connections - terminals Screw connection 0.2…2.5 mm²
Net weight 21.16 kg
Height Outside: 281 mm
Inside: 160 mm
Width Outside: 572 mm
Inside: 470 mm
Height 281 mm
Depth Outside: 72 mm
Inside: 72 mm
Width 572 mm
Depth 72 mm
Environment
IP degree of protection Connectors: IP20
IP30
Environmental characteristic Exposure to damp heat not in service (25...55 °C, RH 95 %) : 28 cycles conforming to IEC 60068-2-30
Salt mist: Kb/2 conforming to IEC 60068-2-52
Exposure to damp heat in service: category C2: 48 hours conforming to IEC 60068-2-56
Ambient air temperature for operation -35…80 °C
Ambient air temperature for storage -55…100 °C
Standards IEC 60947-2
Product certifications CE
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 18.0 cm
Package 1 Width 34.0 cm
Package 1 Length 65.0 cm
Package 1 Weight 17.5 kg
Unit Type of Package 2 P12
Number of Units in Package 2 9
Package 2 Height 75.0 cm
Package 2 Width 80.0 cm
Package 2 Length 120.0 cm
Package 2 Weight 199.668 kg
Offer Sustainability
Packaging without single use plastic No
Packaging made with recycled cardboard No
REACh Regulation
print REACh Declaration
REACh free of SVHC Yes
EU RoHS Directive Compliant
print EU RoHS Declaration
Toxic heavy metal free Yes
Mercury free Yes
RoHS exemption information
print Yes
China RoHS Regulation
print China RoHS declaration
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
California proposition 65 WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Take-back No
Contractual warranty
Warranty 18 months