Network frequency
|
50 Hz
|
[Ue] rated operational voltage
|
400 V AC 50 Hz
|
Maximum power
|
2.1 W at 400 V AC
|
[Ui] rated insulation voltage
|
500 V AC 50/60 Hz
|
[Uimp] rated impulse withstand voltage
|
4 kV
|
Control signal type
|
Maintained
|
Switching frequency
|
100 switching operations/day
|
Local signalling
|
Action indicator
|
Hold-in power consumption in VA
|
6.5 VA
|
Inrush power in VA
|
53 VA
|
Mounting mode
|
Clip-on
|
Mounting support
|
35 mm symmetrical DIN rail
|
9 mm pitches
|
6
|
Height
|
85 mm
|
Width
|
54 mm
|
Depth
|
60 mm
|
Colour
|
White
|
Mechanical durability
|
1000000 cycles
|
Electrical durability
|
100000 cycles IEC/EN 61095 40 A 50 Hz AC-7A
30000 cycles IEC/EN 61095 15 A 50 Hz AC-7B
30000 cycles IEC/EN 61095 50 Hz AC-7C
100000 cycles EN/IEC 60947-4-1 50 Hz AC-1
30000 cycles EN/IEC 60947-4-1 50 Hz AC-3
30000 cycles EN/IEC 60947-4-1 50 Hz AC-5a
30000 cycles EN/IEC 60947-4-1 50 Hz AC-5b
|
Connections - terminals
|
Control circuit: tunnel type terminals2 cable(s) 1.5 mm² rigid
Control circuit: tunnel type terminals1 cable(s) 1.5…2.5 mm² rigid
Power circuit: tunnel type terminals1 cable(s) 6…16 mm² flexible
Power circuit: tunnel type terminals1 cable(s) 6…25 mm² rigid
Control circuit: tunnel type terminals2 cable(s) 1.5…2.5 mm² flexible
|
Tightening torque
|
Control circuit: 0.8 N.m
Power circuit: 3.5 N.m
|
Product compatibility
|
IACTp
IATEt
IACTc
IACTs
|
Compatibility code
|
ICT
|
Market segment
|
Residential
Small commercial
|
Packaging without single use plastic
|
No
|
Packaging made with recycled cardboard
|
No
|
SCIP Number
|
429095ee-388a-4184-bea4-16f87e374975
|
BVB
|
Accepted
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Compliant with Exemptions
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
No need of specific recycling operations
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
Take-back
|
No
|
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle)
|
431
|