Network frequency
|
50/60 Hz
|
Magnetic tripping limit
|
5...10 x In
|
[Ics] rated service breaking capacity
|
6000 A 100 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz
|
Limitation class
|
3 conforming to EN/IEC 60898-1
|
[Ui] rated insulation voltage
|
440 V AC 50/60 Hz conforming to EN/IEC 60898-1
|
[Uimp] rated impulse withstand voltage
|
4 kV conforming to EN/IEC 60898-1
|
Contact position indicator
|
No
|
Control type
|
Toggle
|
Local signalling
|
ON/OFF indication
|
Mounting mode
|
Clip-on
|
Mounting support
|
DIN rail
|
9 mm pitches
|
6
|
Height
|
85 mm
|
Width
|
54 mm
|
Depth
|
78.5 mm
|
Net weight
|
300 g
|
Colour
|
White
|
Mechanical durability
|
20000 cycles
|
Electrical durability
|
10000 cycles
|
Locking options description
|
Padlocking device
|
Connections - terminals
|
Tunnel type terminal (top or bottom) 1…35 mm² rigid
Tunnel type terminal (top or bottom) 1…25 mm² flexible
|
Wire stripping length
|
14 mm for top or bottom connection
|
Tightening torque
|
3.5 N.m top or bottom
|
Earth-leakage protection
|
Without
|