|
|
|
A9MEM1591
energy sensor, PowerTag Rope 600A 3P/3P+N top and bottom position
|
|
|
Main
Range of product
|
PowerLogic
|
Product name
|
PowerTag R600
|
Product or component type
|
Energy sensor
|
Poles
|
3P
3P + N
|
Maximum current [Imax]
|
600 A
|
[Ib] Basic current
|
100 A
|
Starting current
|
400 mA
|
Saturation current
|
1200 A
|
Product specific application
|
Energy management
Overload alarm
Power factor
Load monitoring
Circuit monitoring
|
Concentrator compatibility
|
Acti9 PowerTag Link C
Acti9 PowerTag Link
Acti9 PowerTag Link HD
Harmony Hub
EcoStruxure Panel Server Universal
EcoStruxure Panel Server Advanced
PrismaSet Active
|
Range compatibility
|
Masterpact MasterPact MTZ for switch disconnector
Masterpact MasterPact NW
Masterpact MasterPact NT
ComPact ComPact NS
|
Range compatibility
|
Acti9
TeSys
|
Type of measurement
|
Active and reactive energy
Apparent energy
Active and reactive power
Apparent power
Current
Voltage
Power factor
Internal temperature
Frequency
|
Accuracy class
|
Class 1 active energy conforming to IEC 61557-12
Class 2 reactive energy conforming to IEC 61557-12
Class 2 apparent energy conforming to IEC 61557-12
Class 1 active power conforming to IEC 61557-12
Class 2 reactive power conforming to IEC 61557-12
Class 2 apparent power conforming to IEC 61557-12
Class 1 current conforming to IEC 61557-12
Class 0.5 voltage conforming to IEC 61557-12
Class 1 power factor conforming to IEC 61557-12
Class 0.5 frequency conforming to IEC 61557-12
|
Metering type
|
Active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at total per phase
Active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at partial per phase
Active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at 3-phase total
Active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at 3-phase partial
Reactive energy E -rA- IN/OUT 0...281 x 10exp(9) kVARh at total per phase
Reactive energy E -rA- IN/OUT 0...281 x 10exp(9) kVARh at partial per phase
Reactive energy E -rA- IN/OUT 0...281 x 10exp(9) kVARh at 3-phase total
Reactive energy E -rA- IN/OUT 0...281 x 10exp(9) kVARh at 3-phase partial
Apparent energy E -apA- 0...281 x 10exp(9) kVAh at total per phase
Apparent energy E -apA- 0...281 x 10exp(9) kVAh at partial per phase
Apparent energy E -apA- 0...281 x 10exp(9) kVAh at 3-phase total
Apparent energy E -apA- 0...281 x 10exp(9) kVAh at 3-phase partial
Active power P, P1, P2, P3
Reactive power Q, Q1, Q2, Q3
Apparent power S, S1, S2, S3
Current I1, I2, I3
Calculated neutral current
Voltage U12, U23, U31
Voltage V1N, V2N, V3N
Frequency 45...65 Hz
Power factor at per phase
Power factor at total
|
Mounting location
|
Top or bottom
|
Mounting support
|
Busbar
Cables
|
Product destination
|
Switchboard
|
Event management
|
Voltage loss with measured current at voltage loss
|
Transmission support medium
|
Radio frequency 2.4…2.4835 GHz conforming to IEEE 802.15.4
|
Emission power
|
10 mW
|
Complementary
Mounting mode
|
Clip-on (DIN rail)
|
Electrical connection (voltage sensing & power supply)
|
Removable spring terminal block
|
Cable cross section
|
1 rigid cable 0.2…1.5 mm² without cable end
1 stranded cable 0.2…2.5 mm² without cable end
1 stranded cable 0.25…1.5 mm² with cable end
|
Wire stripping length
|
11 mm
|
Cable length
|
1 m for sensor
|
Current sensor diameter
|
Closed: 100 mm
|
Supply voltage
|
100...277 V AC, +/- 20 %, phase to neutral
173...480 V AC, +/- 20 %, phase to phase
|
Network frequency
|
50 Hz
60 Hz
|
Maximum power consumption
|
3 VA
|
Standards
|
IEC 61557-12
IEC 61010-1
ETSI EN 301 487-1
IEC 61010-2-030
IEC 61326-1
ETSI EN 300 328
|
Number of 9mm pitches on Din rail
|
2
|
Height
|
Base unit: 105 mm
|
Width
|
Base unit: 18 mm
|
Depth
|
Base unit: 67.5 mm
|
Colour
|
White (RAL 9003)
|
Environment
Maximum conductor temperature
|
105 °C
|
Quality labels
|
CE
|
Directives
|
2014/53/EU - radio equipment directive
|
Operating altitude
|
0...2000 m
|
Ambient air temperature for operation
|
-25…70 °C
|
Ambient air temperature for storage
|
-40…85 °C
|
Overvoltage category
|
IV conforming to IEC 61010-1
|
Measurement category
|
Category IV conforming to IEC 61010-2-030
|
IP degree of protection
|
IP20 conforming to IEC 60529
|
IK degree of protection
|
IK05
|
Pollution degree
|
3
|
Relative humidity
|
0…95 % at 55 °C conforming to IEC 60721-3-3
|
Vibration resistance
|
3M4 conforming to IEC 60721-3-3
|
Electromagnetic compatibility
|
Industrial electromagnetic environment conforming to IEC 61326-1
Radiated EMC conforming to ETSI EN 301 489-17
Electromagnetic emission conforming to IEC 62311
|
Environmental characteristics
|
Indoor use
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
8.200 cm
|
Package 1 Width
|
17.500 cm
|
Package 1 Length
|
20.000 cm
|
Package 1 Weight
|
559.000 g
|
Unit Type of Package 2
|
S03
|
Number of Units in Package 2
|
7
|
Package 2 Height
|
30.000 cm
|
Package 2 Width
|
30.000 cm
|
Package 2 Length
|
40.000 cm
|
Package 2 Weight
|
4.424 kg
|
Offer Sustainability
Sustainable offer status
|
Green Premium product
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Compliant with Exemptions
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
California proposition 65
|
"WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov"
|
|
|