Poles description
|
3P
1P + N
3P + N
|
Type of measurement
|
Active energy
|
Device application
|
Partial meter
Sub billing
|
Accuracy class
|
Class 0.5S active energy conforming to IEC 62053-22
Class 0.5S active energy conforming to IEC 61557-12
Class C active energy conforming to EN 50470-3
|
Input type
|
External CT 1 A or 5 A
|
[In] rated current
|
5 A
1 A
|
Rated voltage
|
100…277 V
173…480 V
|
Network frequency
|
50 Hz
60 Hz
|
Technology type
|
Electronic
|
Display type
|
LCD display
|
Sampling rate
|
32 samples/cycle
|
Measurement current
|
1…32767000 mA
|
Maximum value measured
|
99999999 MWh
|
Communication port protocol
|
-
|
Communication port support
|
-
|
Local signalling
|
Green indicator light: power ON
Yellow flashing LED: accuracy checking
|
Number of inputs
|
0
|
Number of outputs
|
1 pulse
|
Mounting mode
|
Clip-on
|
Mounting support
|
DIN rail
|
Connections - terminals
|
Current circuit: screw terminals 6 mm² cable(s)
Voltage circuit: screw terminals 2.5 mm² cable(s)
|
Overvoltage category
|
III
|
Standards
|
IEC 61036
UL 61010-1
IEC 61557-12
IEC 62053-22
IEC 61010
IEC 62053-23
|
Product certifications
|
CE conforming to IEC 61010 (safety)
CE conforming to EN 61557-12 (power monitor)
CE conforming to IEC 61326-1 (EMC)
CULus conforming to UL 61010 (safety)
CULus conforming to ANSI C12.20 (sub-meter)
EAC (sub-meter)
RCM conforming to NMI M 6-1 (sub-meter)
UL
MID conforming to EN 50470-3 (sub-meter)
MID conforming to EN 62052 (sub-meter)
|